Battery recharge rate
(included batteries)
Less than 4 hours from 10% to 90%
Replacement battery
cartridge (internal UPS
battery replacement)
RBC94-3U
(quantity 3)
Battery Access
Front panel battery access door
Battery replacement
description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage regulation
description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 167 to 260
Overvoltage correction
Input voltages between 228V and 260V are reduced by 12%
Undervoltage correction
Input voltages between 167V and 194V are boosted by 12%
LEDS ALARMS & SWITCHES
LED Indicators
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Alarms
Audible alarm indicates power-failure, overload and low-battery conditions
Alarm cancel operation
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate
low-battery status
Switches
2 Switches control off/on power status and alarm-cancel/self-test operation
SURGE / NOISE SUPPRESSION
UPS AC suppression joule
rating
1020
UPS AC suppression
response time
Instantaneous
EMI / RFI AC noise
suppression
Yes
PHYSICAL
Installation form factors
supported with included
accessories
4 post 19 inch rackmount
Installation form factors
supported with optional
accessories
2 post rackmount (2POSTRMKITWM); Tower (2-9USTAND)
Primary form factor
Rackmount
UPS / Power Module
dimensions in primary form
factor (height x width x
depth / inches)
5.25 x 17.5 x 25
UPS / Power Module
dimensions in primary form
factor (height x width x
depth / cm)
13.3 x 44.4 x 63.5
Rack Height
3U
Secondary form factor
Tower (requires
2-9USTAND
)
UPS / Power Module weight
(lbs)
143.3