background image

UPS / Power Module weight
(kg)

65.1

UPS Shipping dimensions
(height x width x depth /
inches)

11.2 x 23 x 31.5

UPS Shipping dimensions
(height x width x depth / cm)

28.6 x 58.4 x 80

Shipping weight (lbs)

181.9

Shipping weight (kg)

82.6

Cooling method

Fan

UPS housing material

Steel

ENVIRONMENTAL

Operating Temperature
Range

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius

Storage Temperature Range

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius

Relative Humidity

0 to 95%, non-condensing

AC mode BTU / hr. (full
load)

366

COMMUNICATIONS

Communications interface

USB; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface

Network monitoring port
description

Supports detailed monitoring of UPS and site power conditions

PowerAlert software

Included

Communications cable

USB and DB9 cabling included

WatchDog compatibility

Supports Watchdog application, OS and hard-reboot restart options for remote applications

LINE / BATTERY TRANSFER

Transfer time

7 milliseconds (AC to Battery), 1 millisecond (Battery to AC)

Low voltage transfer to
battery power (setpoint)

167

High voltage transfer to
battery power (setpoint)

260

SPECIAL FEATURES

Grounding lug

Back panel grounding lug

Cold Start (startup in
battery mode during a
power failure)

Cold-start operation supported

High availability UPS
features

Hot swappable batteries

Green & high efficiency
features

Greater than 95% efficiency - GREEN UPS

CERTIFICATIONS

UPS Certifications

Tested to UL1778 (USA); Tested to CSA (Canada); Meets FCC Part 15 Category A (EMI)

WARRANTY

Reviews: