Basic Operation 

continued

Indicator Lights (Front Panel)

“MUTE/TEST” Button
• To Silence (or “Mute”) UPS Alarms:

briefly press and release the

MUTE/TEST button.

• To Run a Self-Test:

with your UPS plugged in and turned ON, press

and hold the MUTE/TEST button for two seconds.* Continue holding
the button until the alarm beeps several times and the UPS performs
a self test. See “Results of a Self-Test” below. Note: you can leave
connected equipment on during a self-test. Your UPS, however, will
not perform a self-test if the UPS is not turned on (see
“ON/OFF/STANDBY” Button description).

CAUTION! Do not unplug your UPS to test its batteries. This
will remove safe electrical grounding and may introduce a
damaging surge into your network connections.

Results of a Self-Test: 

the test will last approximately 10 seconds as

the UPS switches to battery to test its load capacity and battery charge.

• 

If the “OUTPUT LOAD LEVEL” LED remains lit red and the alarm
continues to sound after the test, the UPS’s outlets are overloaded. To
clear the overload, unplug some of your equipment and run the self-test
repeatedly until the “OUTPUT LOAD LEVEL” LED is no longer lit
red and the alarm is no longer sounding.

CAUTION! Any overload that is not corrected by the user
immediately following a self-test may cause the UPS to shut
down and cease supplying output power in the event of a
blackout or brownout.

• 

If the “BATTERY WARNING” LED remains lit and the alarm con-
tinues to sound after the test, the UPS batteries need to be recharged
or replaced. Allow the UPS to recharge continuously for 12 hours,
and repeat the self-test. If the LED remains lit, contact Tripp Lite for
service. If your UPS requires battery replacement, visit 
www.tripplite.com to locate the specific Tripp Lite replacement bat-
tery for your UPS.

* The alarm will beep once briefly after the indicated interval has passed.

All Indicator Light descriptions apply when the UPS is plugged into a wall outlet and turned ON.

“POWER” LED:

this green LED lights continuously when the UPS is

ON and supplying connected equipment with AC power from a utility
source. The LED flashes and an alarm sounds (4 short beeps followed
by a pause) to indicate the UPS is operating from its internal batteries dur-
ing a blackout or severe brownout. If the blackout or severe brownout is 
prolonged, you should save files and shut down your equipment since
internal battery power will eventually be depleted. See “BATTERY
CHARGE” LED description below.

200404080 932245 SMARTINT22003000VS OM.qxd  5/26/2004  4:26 PM  Page 6

Summary of Contents for SMARTINT3000VS

Page 1: ...on 5 Storage Service 10 Specifications 10 Models SMARTINT2200VS SMARTINT3000VS Intelligent Line Interactive UPS Systems Tower Configuration 230V Input 2200VA 3000VA Capacities Extended Run Options SMARTINT3000VS model Copyright 2004 Tripp Lite All rights reserved SmartPro is a registered trademark of Tripp Lite Español 11 Français 22 Optional Installation 4 Póññêèé 33 ...

Page 2: ...ut of your UPS Battery Warnings Batteries can present a risk of electrical shock and burn from high short circuit current Observe proper precautions Do not dispose of the batteries in a fire Do not open the UPS or batteries Do not short or bridge the battery terminals with any object Unplug and turn off the UPS before performing battery replacement Use tools with insulated handles There are no use...

Page 3: ...all 773 869 1234 order part P004 006 Your UPS is designed to support only com puter equipment You will overload the UPS if the total VA ratings for all the equipment you connect exceeds the UPS s Output Capacity see Specifications To find your equipment s VA ratings look on their nameplates If the equipment is listed in amps multiply the number of amps by 230 to determine VA Example 1 amp 230 230 ...

Page 4: ...ternal Battery Connection select models Your UPS comes with a robust internal battery system external batteries are only needed to extend runtime Adding external batteries will increase recharge time as well as runtime The illustration see shows the location of your UPS s External Battery Connector where you will insert the battery pack cable Complete installation instructions for your battery pac...

Page 5: ...PLUG 5 4 3 2 NO CONNECTION N O EPO SWITCH 4a 4b Basic Operation Buttons ON OFF STANDBY Button To turn the UPS ON with the UPS plugged into a liveAC wall outlet press and hold the ON OFF STANDBY button for one second Release the button If utility power is absent you can cold start the UPS i e turn it ON and supply power for a limited time from its batteries by pressing and holding the ON OFF STANDB...

Page 6: ...o longer lit red and the alarm is no longer sounding CAUTION Any overload that is not corrected by the user immediately following a self test may cause the UPS to shut down and cease supplying output power in the event of a blackout or brownout If the BATTERY WARNING LED remains lit and the alarm con tinues to sound after the test the UPS batteries need to be recharged or replaced Allow the UPS to...

Page 7: ...rging and green indicates the batteries are fully charged When the UPS is operating from battery power during a blackout or severe brownout this LED indicates the approximate amount of energy ultimately affecting runtime which the UPS s batteries will provide red indicates a low level of energy yellow indicates a medium level of energy and green indicates a high level of energy Since the runtime p...

Page 8: ...re to monitor a wide variety of AC line power and UPS operating conditions Consult your PowerAlert Software manual or contact Tripp Lite Customer Support for more information See USB Communications and RS 232 Serial Communications in the Optional Installation section for installation instructions EPO Port select models Your UPS features an EPO port that may be used to connect the UPS to a contact ...

Page 9: ...l battery system Power Sensitivity Adjustment This dial is normally set fully counter clockwise which enables the UPS to provide maximum protection against waveform distortions in its AC input When such distortion occurs the UPS will normally switch to providing PWM sine wave power from its battery reserves for as long as the distortion is present In areas with poor utility power or where the UPS ...

Page 10: ...an can arrange to send you proper packaging Securely pack the UPS to avoid damage during shipping Do not use Styrofoam beads for packaging Any damages direct indirect special incidental or consequential to the UPS incurred during shipment to Tripp Lite or an authorized Tripp Lite service center is not covered under warranty UPS Systems shipped to Tripp Lite or an authorized Tripp Lite service cent...

Page 11: ...1111 W 35th Street Chicago IL 60609 USA 773 869 1234 USA 773 869 1212 International www tripplite com ...

Reviews: