22
Output Settings
Note: Any Output Setting changes require a UPS power cycle.
Output Voltage:
Used to set the UPS’ output voltage rating. From the SETUP MENU screen, scroll DOWN
i
until you reach the
OUTPUT SETTING screen. Press ON to reach an OUTPUT VOLTAGE screen and ON again. You can now scroll DOWN
i
or UP
h
between 5 voltage values: 200/208/220/230/240V. Press ON to save your desired voltage. DEFAULT is set to 208V.
Frequency Converter:
Used to set the Frequency Converter Mode. From the SETUP MENU screen, scroll DOWN
i
until you reach
the OUTPUT SETTING screen. Press ENTER for the OUTPUT VOLTAGE screen and DOWN
i
to access the FREQ CONVERTER screen.
Here, press ON. Now you can scroll DOWN
i
or UP
h
between DISABLE, 50 and 60 Hz. Press ON to save your selection. When on
DISABLE, the UPS will automatically detect input frequency and select 50 or 60 Hz accordingly. The DEFAULT selection is DISABLE.
Operation
(continued)
OUTPUT SETTING
ENT DOWN UP
OUTPUT SETTING
ENT DOWN UP
OUTPUT VOLTAGE
ENT DOWN UP
OUTPUT VOLTAGE
ENT DOWN UP
FREQ. CONVERTER
ENT DOWN UP
*230V*
ENT DOWN UP
*DISABLE*
ENT DOWN UP
220V
ENT DOWN UP
50Hz
ENT DOWN UP
208V
ENT DOWN UP
60Hz
ENT DOWN UP
200V
ENT DOWN UP
240V
ENT DOWN UP
To ENTER
To ENTER