21
Operations
Front Panel LCD Selection and Configuration Options
MAIN MENU / SUBMENU
DISPLAY / SETTING OPTIONS
DISPLAY / SETTING DESCRIPTION
STATUS
Load Status
• Load level (%, kW, kVA, A, PF)
• Available capacity (%, kW, kVA)
UPS load percent (%), kilowatt (kW), kilovoltamp
(kVA), amp (A) & power factor (PF).
UPS capacity available in percent (%), kilowatts (kW)
& kilovoltamps (kVA).
In/Out Status
• Input voltage & frequency (Vac, Hz)
• Output voltage & frequency (Vac, Hz)
• Load Group 1 (On, Off)
• Load Group 2 (On, Off)
• Load Group 3 (On, Off)
Displays UPS input and output status information for input / output
voltage (Vac), frequency (Hz) and outlet group power status (On/
Off) information.
Energy Status
• Efficiency (%)
• Avg. Power (kw/hr.)
• Configured power strategy
Displays UPS efficiency percentage (%), connected equipment
kilowatt hour consumption (kw/hr.) and configured power strategy.
Battery Status
• Battery model & serial number
• Installed (mm/dd/yyyy)
• Expires (mm/dd/yyyy)
Displays Battery Pack model number & serial number (Tripp Lite
SMART BATTERY PACKS) only, installation date and user configured
expiration date.
Power Flow Chart
• View UPS operational flow chart
Displays UPS operating mode in a graphical flow chart.
CONTROL
Start Batt. Test
• Initiates a manual battery test
Initiates a momentary UPS battery self-test with immediate Pass/
Fail results.
Reset Fault State
• Resets any fault state messages
Use this option to clear UPS fault messages.
Auto Batt. Testing
• Set regular battery self-test interval
o Disable
o 4 weeks (factory setting)
o 13 weeks
o 26 weeks
Use this option to initiate automatic UPS battery testing at regular
intervals.
EVENT LOG
On Batt. Events
• Event counter
(UPS On-battery events only)
• Total minutes (total minutes of
on-battery mode operation)
• Most recent power failure (date)
• Months until battery replacement alert
(months)
• Event details (date, time &
description for the last 20 logged events)
Displays a summary of all ON-BATTERY events where the UPS
switched to battery mode in response to a protected condition.
Event details lists the last 20 battery events. As additional alerts
occur, the oldest records will be automatically removed.
All Events
• Event counter (all events)
• Most recent event (date)
• Date time log
Displays a summary of all Recorded events. Event details lists the
last 20 events. As additional alerts occur, the oldest records will
be automatically removed.
SETTINGS
Basic setup
System
• Current date (display, set date)
• Current time (display, set time)
• Audible alarm (enable, disable)
• Language (select)
Displays, sets and resets date, time, audible alarm status and
language settings.
Note:
Audible Alarm DISABLE setting prevents power fail and
operating fault alarms only, the UPS will always “beep” to confirm
the UPS is accepting user input from the front-panel LCD
navigation buttons.
Note:
The current date and current local time are reported directly
from the remote management card.
Output voltage
• 200
• 208
• 220
• 230
• 240
Use the SETTINGS / BASIC / OUTPUT VOLTAGE option to display or
set the nominal UPS output voltage (changes take effect on next
restart).
Summary of Contents for SmartOnline AG-0358 Series
Page 106: ...106 0 3 smart Tripp Lite BP192V12RT3US...
Page 108: ...108 BP192V12RT3US 1 2 3 4 1 2 3 Smart Battery 4...
Page 109: ...109 1 2 5 7 6 8 5 6 7 8 1...
Page 122: ...122 0 5 60 60 0 5 50 60 50 0 5 FREQUENCY CONVERSION FREQUENCY CONVERSION...
Page 133: ...1 2 5 6 9 7 8 133 5 6 7 8 9 1...
Page 134: ...1 5 3 134 tripplite com support 1 2 2 3 4 3 2 5 1...