Maintains full-time sine wave output within 2% of 208/120V nominal at 60Hz during brownouts as low 100V and overvoltages as high as

300V

Expandable runtime is supported with optional BP240V10RT3U; BP240V557C-1PH; BP240V787C-1PH; BP240V1037C-1PH;

BP240V1407C-1PH external battery packs

 Some external battery configurations require the use of Tripp Lite's 

External Battery Configuration Software

 (see manual) 

Highly efficient operation in optional economy mode significantly reduces BTU heat output and operating energy costs

Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries

are expired and require replacement

PowerAlert monitoring software offers detailed site power and UPS updates with support for safe auto-shutdown of connected systems as

UPS batteries become depleted

Includes Free PowerAlert monitoring software packages; PowerAlert LOCAL for desktops and small business networks, PowerAlert NSA

(Network Shutdown Agent) for larger networks and PowerAlert NMS (Network Management System) for monitoring up to 250

SNMP-enabled UPS, PDU and other networking devices

Supports detailed monitoring of equipment load levels, self-test data and utility power conditions via built-in RS-232 and USB interfaces

HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X

Optional SNMPWEBCARD offers communications and control via secure remote web and network interfaces

Optional RELAYIOCARD supports six configurable hard contact closure outputs for custom event notification

Optional RELAYIOMINI interface module offers three configurable hard contact closure outputs for custom event notification (requires

removal of USB interface module)

Supports Emergency Power Off (EPO) via built-in interface

Included rail kit supports 8U 19 inch rackmount installation in 4 post racks

Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks

Front panel LEDs and LCD readout with scroll controls and password option supports visual monitoring of all major UPS functions and

advanced UPS settings for charge level, nominal voltage selection and other operational parameters

LED / LCD display panel rotates for viewing in rackmount or tower configurations

Network-grade AC surge and noise suppression

Industrial mode option (factory preset) enables supports high current startup loads by momentarily switching to bypass mode in response to

short duration overload conditions

External battery packs are field replaceable and hot swappable

Specifications

OUTPUT

Output Volt Amp
Capacity (VA)

10000

Output kVA capacity
(kVA)

10

Output Watt
Capacity (watts)

9000

Output kW capacity

9.0

Output power factor

0.9

Output Capacity
Details

Supports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30
seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power;
Double conversion mode is automatically restored as load levels are reduced to 95% or less

Nominal Output
Voltage(s) Supported

120V; 208V

Frequency
compatibility

60 Hz

Frequency
compatibility details

Output frequency regu/- 0.05Hz (free running)

Output voltage
regulation (line
mode)

+/- 2%

Summary of Contents for SmartOnline SU10000RT3U2TF

Page 1: ...wap replacement options make this UPS ideal for advanced networking applications in data centers computer rooms network closets and rugged industrial locations Package Includes SU10000RT3UPM 3U UPS po...

Page 2: ...IOCARD supports six configurable hard contact closure outputs for custom event notification Optional RELAYIOMINI interface module offers three configurable hard contact closure outputs for custom even...

Page 3: ...S input connection description 3 wire single phase input L1 L2 G Recommended Electrical Service 60A Phase Single Phase BATTERY Full load runtime minutes 4 3 min 9000w Half load runtime minutes 12 5 mi...

Page 4: ...e scrolling LCD functions bundled PDU includes bypass switch to enable hot swap UPS power module replacement SURGE NOISE SUPPRESSION UPS AC suppression response time Instantaneous EMI RFI AC noise sup...

Page 5: ...luded battery pack dimensions height x width x depth inches 5 25 x 17 5 x 25 Included battery pack dimensions height x width x depth cm 13 3 x 44 4 x 63 5 Included battery pack weight lbs 158 7 Includ...

Page 6: ...double conversion mode Transfer time economy mode 8 ms typical power failure response in optional economy mode Low voltage transfer to battery power setpoint 100V High voltage transfer to battery pow...

Page 7: ...ackmount NEMA 5 15 20R outlets NEMA L5 20P input with 5 20P adapter 1 PDUMNV20HV Monitored PDU Power Distribution Unit supports real time remote monitoring of load level voltage and frequency with opt...

Page 8: ...Power Adapter cord NEMA L5 20R to NEMA 5 20P 1 More information including related products owner s manuals and additional technical specifications can be found online at www tripplite com en products...

Reviews: