types
Maintains full-time sine wave output within 2% of 208/120V nominal at 60Hz during brownouts as low 100V and overvoltages as high as
300V
Expandable runtime is supported with optional BP240V10RT3U; BP240V557C-1PH; BP240V787C-1PH; BP240V1037C-1PH;
BP240V1407C-1PH external battery packs
Some external battery configurations require the use of Tripp Lite's
External Battery Configuration Software
(see manual)
Highly efficient operation in optional economy mode significantly reduces BTU heat output and operating energy costs
Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries
are expired and require replacement
PowerAlert monitoring software offers detailed site power and UPS updates with support for safe auto-shutdown of connected systems as
UPS batteries become depleted
Includes Free PowerAlert monitoring software packages; PowerAlert LOCAL for desktops and small business networks, PowerAlert NSA
(Network Shutdown Agent) for larger networks and PowerAlert NMS (Network Management System) for monitoring up to 250
SNMP-enabled UPS, PDU and other networking devices
Supports detailed monitoring of equipment load levels, self-test data and utility power conditions via built-in RS-232 and USB interfaces
HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Optional SNMPWEBCARD offers communications and control via secure remote web and network interfaces
Optional RELAYIOCARD supports six configurable hard contact closure outputs for custom event notification
Optional RELAYIOMINI interface module offers three configurable hard contact closure outputs for custom event notification (requires
removal of USB interface module)
Supports Emergency Power Off (EPO) via built-in interface
Included rail kit supports 8U 19 inch rackmount installation in 4 post racks
Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks
Front panel LEDs and LCD readout with scroll controls and password option supports visual monitoring of all major UPS functions and
advanced UPS settings for charge level, nominal voltage selection and other operational parameters
LED / LCD display panel rotates for viewing in rackmount or tower configurations
Network-grade AC surge and noise suppression
Industrial mode option (factory preset) enables supports high current startup loads by momentarily switching to bypass mode in response to
short duration overload conditions
External battery packs are field replaceable and hot swappable
Specifications
OUTPUT
Output Volt Amp
Capacity (VA)
10000
Output kVA capacity
(kVA)
10
Output Watt
Capacity (watts)
9000
Output kW capacity
9.0
Output power factor
0.9
Output Capacity
Details
Supports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30
seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power;
Double conversion mode is automatically restored as load levels are reduced to 95% or less
Nominal Output
Voltage(s) Supported
120V; 208V
Frequency
compatibility
60 Hz
Frequency
compatibility details
Output frequency regu/- 0.05Hz (free running)
Output voltage
regulation (line
mode)
+/- 2%