Relative Humidity
0 to 95%, non-condensing
AC mode BTU / hr.
(full load)
3415
AC economy mode
BTU / hr. (full load)
1275
AC economy mode
efficiency rating
(100% load)
96%
Operating Elevation
(ft.)
0-3000m (0 to 10,000 ft.)
Audible Noise
60 dBA at front side 1 meter
Operating Elevation
(m)
0-3000 m
COMMUNICATIONS
Communications
interface
USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Network monitoring
port description
Additional contact closure support with optional RELAYIOCARD and RELAYIOMINI interface cards. RELAYIOMINI
installation requires removal of panel containing USB ports
PowerAlert software
Included
Communications
cable
USB, DB9 serial and EPO cables included
WatchDog
compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
LINE / BATTERY TRANSFER
Transfer time
No transfer time (0 ms.) in online, double-conversion mode
Transfer time
(economy mode)
8 ms. typical power failure response in optional economy mode
Low voltage transfer
to battery power
(setpoint)
100V
High voltage transfer
to battery power
(setpoint)
300V
SPECIAL FEATURES
Cold Start (startup in
battery mode during
a power failure)
Cold-start operation supported
Economy mode
operation
Optional economy mode enables high efficiency bypass operation with a maximum output voltage variation of
+/-10%. Double conversion mode is automatically restored as mains voltage varies /-10% with less than 1
millisecond transfer time between modes.
High availability UPS
features
Automatic inverter bypass; Manual bypass switch; Detachable hot-swap PDU; Hot swappable UPS power module;
Hot swappable batteries
Green & high
efficiency features
High efficiency economy mode operation; Schedulable daily hours of economy mode operation
CERTIFICATIONS
UPS Certifications
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)
UPS Certification
details
IEC 61000-4-5 1995 B Surge Immunity