background image

Uses only 2 rack spaces (2U) in standard 19 inch rack

Fault tolerant auto-bypass maintians continuous utility output to connected equipment, even in cases where the UPS is overloaded or

suffers an internal failure that requires service

DB9 serial port for network interface; SNMP compatible

Slot for optional SNMP/web card (part# SNMPWEBCARD) 

PowerAlert unattended shutdown software and 6 ft. network cable included 

Compatible with Tripp Lite's Watchdog system service software

Diagnostic LEDs

Battery replacement door 

Mounting hardware included for 4 post rack enclosures, 2 post telecom rack compatible with separate purchase 2POSTRMKIT accessory

2 year manufacturers product warranty 

$250,000 Ultimate Lifetime 

connected equipment insurance

Specifications

OUTPUT

Frequency
compatibility

50 / 60 Hz

Output VA

1000

Output watts

800

Output nominal
voltage

120V AC

Output voltage
regulation

Maintains full-time sine wave output within 2% of 120V, less than 5% total harmonic distortion

Output frequency
regulation

Regulates line frequency to 50/60Hz +/- 0.05Hz

Overload protection

15A input breaker

Outlet quantity /
type

6 NEMA 5-15R

Customized load
management
receptacles

"2 individually controllable load banks support automated load shedding and remote reboot on demand of locked
network devices. Configurable via PowerAlert software to automatically switch off optional loads, like monitors, to
increase available runtime for servers and other critical devices. (bank A consists of 4 outlets / bank B consists of 2
outlets)"

INPUT

UPS Input cord
length (ft.)

6 ft. 14 gauge

Recommended
Electrical Service

15A 120V

Maximum Input
Amps (A)

8.6

Maximum Input
Watts

955

Input connection
type

NEMA 5-15P

Voltage
compatibility (VAC)

120

BATTERY

Expandable battery
runtime

Supports extended runtime with optional external battery pack BP36V142u (multi-pack compatible)

Summary of Contents for SmartOnline SU1000RTXL2U

Page 1: ... or shed less critical loads to extend battery runtime for more critical equipment Battery support can be extended indefinitely through the addition of external 2U rackmount battery packs part BP36V142U Includes slot for internal SNMP web card plus DB9 enhanced serial monitoring port for unattended shutdown remote control and monitoring of UPS system and power data Compatible with Tripp Lite s Wat...

Page 2: ...watts 800 Output nominal voltage 120V AC Output voltage regulation Maintains full time sine wave output within 2 of 120V less than 5 total harmonic distortion Output frequency regulation Regulates line frequency to 50 60Hz 0 05Hz Overload protection 15A input breaker Outlet quantity type 6 NEMA 5 15R Customized load management receptacles 2 individually controllable load banks support automated lo...

Page 3: ...20V 2 during undervoltages to 80V AC Severe brownout correction At load levels less than 70 UPS maintains output of 120V 2 during undervoltages to 65V AC LEDS ALARMS SWITCHES Alarms Multi function audible alarm offers notification of UPS start backup operation low battery warning overload UPS fault and remote shutdown Switches Includes main power off on switch plus 1 switch to select battery charg...

Page 4: ...s incoming AC to DC then back to AC When commercial power is interrupted UPS maintains continuous output from battery reserves with absolutely no disruption in output AC power Low voltage transfer to battery power Maintains continuous operation during undervoltages as low as 80V 65V at load levels under 70 Below this switchover point output is supported from battery derived AC power High voltage t...

Page 5: ...l rights reserved All trademarks are the sole property of their respective owners Tripp Lite has a policy of continuous improvement Specifications are subject to change without notice Photos may differ slightly from final products ...

Reviews: