9 – Troubleshooting

If the UPS system malfunctions during operation, check the following:
•  Is the input and output wiring correct? 
•  Is the utility AC input voltage within the acceptable range for the UPS system?

If problems persists, please refer to the instructions below. If the problem continues to persist after following the instructions below and/or 
restarting the UPS system, contact Tripp Lite for service.

Problem

LCD Screen Error Code

Possible Solution

Fault LED

Er05 + 

 + 

 

Check the battery connection, then recharge the battery for 12 hours. If the 
problem persists, contact Tripp Lite for service and/or battery replacement.

Fault LED

Er06/Er10/Er12/Er28 + 

If the breaker has tripped, turn off the UPS system completely and allow 
it to cool. Remove some of the load from the UPS output, then reset the 
breaker and restart the UPS. If any of the wiring appears to be damaged, 
replace it.

Fault LED

EPO

Remove the EPO terminal short circuit.

Fault LED

Er11/Er33

Remove any objects blocking the ventilation holes. Make sure the UPS 
location provides adequate ventilation.

Fault LED

Er14

Check the cooling fans on the rear panel. If the problem persists, contact 
Tripp Lite for service.

Fault LED

Er15

Make sure the UPS is operating in normal mode. If it is operating in CVCF 
mode, restart the UPS.

Fault LED

Er16/Er27

All parallel UPS parameters except ID number must be same. Adjust the 
parameters.

Fault LED

Er21

Reconnect the RJ45 cable or set a UPS with ID=1.

Fault LED

Other Error Code

Have a qualified electrician check the AC supply circuit and wiring, then 
restart the UPS system. If the problem persists, contact Tripp Lite for 
service.

UPS fails to offer battery 
backup or backup time is 
much shorter than calculated.

Not Applicable

Recharge the battery uninterrupted for 12 hours. If the problem persists, 
contact Tripp Lite for service and/or battery replacement.

UPS locks itself and cannot 
be turned off.

Not Applicable

Attempt to restart the UPS system (see below). If the problem persists, 
contact Tripp Lite for service.

UPS Detects Error While in Self-Test Mode

If a serious abnormal condition occurs, the UPS system will lock itself in the “OFF” position 

AAA

 and the fault LED will illuminate on the 

control panel. After three seconds, all messages will be locked except for bypass messages (

 and 

). If the AC utility input power 

becomes abnormal after the UPS locks, the 

 LED will go out and 

 will appear on the LCD.  

To release the UPS system lock:

1.  Troubleshoot the UPS system problem using the chart above.

2.  Press the “OFF”   button for five seconds until the buzzer sounds twice, then release the button.
3.  Turn off the utility input breaker.

4.  Restart the UPS system by following the instructions in 

Section 6-3 – Normal Mode Startup

.

5.  If the problem persists, contact Tripp Lite for service.

UPS Off

Summary of Contents for SmartOnline SU10KRT1X

Page 1: ...Mounting 5 4 1 Unpacking 5 4 2 Placement 6 4 3 Mounting Rack 6 4 4 Mounting Tower 7 5 Wiring 8 5 1 Wiring Preparation 8 5 2 Terminal Block Diagram 8 5 3 Electrical and Cable Data 8 5 4 AC Input Output...

Page 2: ...tilation openings of the UPS system or otherwise impede the airflow from the front to the rear of the UPS system Do not place any object on the UPS system especially containers of liquid Spilling liqu...

Page 3: ...damage the UPS system and create a risk of personal injury and property damage Wiring should be performed by trained qualified electricians only Battery Warnings Allow batteries to charge uninterrupt...

Page 4: ...Note Remove the network card in order to use the RS 232 port B Settings Switch for Parallel Redundancy Operation C CAN Bus Connection Ports for Parallel Redundancy Operation D Cooling Fans E External...

Page 5: ...unit Inspect the unit carefully prior to installation If anything appears to be damaged contact Tripp Lite for service Retain the packing materials for future use Packing List 1 UPS Power Module 1 Ext...

Page 6: ...tact the manufacturer of the rack or rack enclosure for a solution 4 Post Mounting Procedure Note The mounting procedure is identical for the external battery pack and the UPS power module Mount the e...

Page 7: ...ition Pull the panel out slightly rotate it and push it back into place Tower Mounting Procedure 1 Use M4 flat head screws S2 to attach covers A5 to four of the tower feet A4 2 Use M3 flat head screws...

Page 8: ...y pack Mark all cables according to their correct purpose polarity phase and diameter Review the diagram in Section 5 2 to familiarize yourself with the terminal block Consult the table in Section 5 3...

Page 9: ...eves through the knockouts in the terminal block cover A2 Each input output wire should terminate with a ring terminal 3 Connect the ring terminal for each input output cable to the appropriate input...

Page 10: ...system 1 Switch the external battery pack s DC breaker to the OFF position 2 Remove the terminal covers from the UPS power module s external battery pack DC cable connector and the external battery pa...

Page 11: ...in economy mode 6 Fault LED This red LED illuminates when UPS system experiences a fault or other abnormal condition If the condition persists after restarting the UPS system refer to Section 9 Troubl...

Page 12: ...f temperature voltage amperage level percentage and frequency Indicates the category being measured line load battery EPO Emergency Power Off Code Description Er05 Battery Weak or Dead Er06 Output Sho...

Page 13: ...and the battery charger begins to charge the external battery pack 8 Press the ON button for approximately 3 seconds then release it The UPS will beep twice and the LCD screen will change from B to C...

Page 14: ...elapsed you will need to repeat the previous step 5 The UPS system will run a self test and display H again Battery mode startup is successful and connected equipment will operate until the battery i...

Page 15: ...tely three seconds until the buzzer sounds twice then release the buttons Except for buzzer Q1 Q2 and self test R1 R2 all other default settings may now be changed by pressing the Previous Change Sett...

Page 16: ...upply circuit is securely grounded Start up Procedure 1 Position the UPS systems as specified above 2 Connect the parallel communication cables C1 C2 to the Ring loop at a maximum length of 7 m Secure...

Page 17: ...rting the EPO terminals activates the EPO emergency power off function which provides emergency shutdown of the UPS system Note The network card must be removed in order to use the UPS system s RS 232...

Page 18: ...t LED Er16 Er27 All parallel UPS parameters except ID number must be same Adjust the parameters Fault LED Er21 Reconnect the RJ45 cable or set a UPS with ID 1 Fault LED Other Error Code Have a qualifi...

Page 19: ...tility power source Next disconnect all equipment The UPS system must be stored in a clean secure environment with a temperature less than 40 C and a relative humidity less than 90 non condensing Note...

Page 20: ...he batteries are designed for hot swap replacement i e replacement while the UPS system is in ON mode but some qualified service personnel may wish to put the UPS system in OFF mode and disconnect equ...

Page 21: ...cific legal rights and you may have other rights which vary from jurisdiction to jurisdiction Tripp Lite 1111 W 35th Street Chicago IL 60609 USA WARNING The individual user should take care to determi...