8
1
4
3
2
5
A1
A3
A3
A2
A2
S5
S5
5 – Wiring
continued
5-4 AC Input/Output Wiring Instructions
5-3 Electrical and Cable Data
AC Input and Output (75°C Minimum Copper Wire)
Maximum Current
Conductor Diameter
Torque Force
54.3 amperes
4.6 mm (#6 AWG)
2.60 N•m (23 in•lb)
1
Use M3 pan-head screws
S5
to attach the cable attachment tray
A1
beneath the terminal block.
2
Route the AC input/output wiring through cable sleeves and route the cable sleeves through the knockouts in the terminal block cover
A2
.
Each input/output wire should terminate with a ring terminal.
3
Connect the ring terminal for each input/output cable to the appropriate input/output terminals. Tighten the terminals with at least 2.60 N•m
of torque.
4
Secure the input/output cable bundles to the cable attachment tray with the included mounting ties
A3
.
5
Use M3 pan-head screws
S5
to secure the terminal block cover
A2