background image

Maintains full-time sine wave output within 2% of 208/240 and 120V nominal at 50/60Hz during brownouts as low 100V and overvoltages as

high as 300V

Expandable runtime is supported with optional BP240V10RT3U; BP240V557C-1PH; BP240V787C-1PH; BP240V1037C-1PH;

BP240V1407C-1PH external battery packs

 Some external battery configurations require the use of Tripp Lite's 

External Battery Configuration Software

 (see manual)

Highly efficient operation in optional economy mode significantly reduces BTU heat output and operating energy costs

Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries

are expired and require replacement

PowerAlert monitoring software offers detailed site power and UPS updates with support for safe auto-shutdown of connected systems as

UPS batteries become depleted

Includes Free PowerAlert monitoring software packages; PowerAlert LOCAL for desktops and small business networks, PowerAlert NSA

(Network Shutdown Agent) for larger networks and PowerAlert NMS (Network Management System) for monitoring up to 250

SNMP-enabled UPS, PDU and other networking devices

Supports detailed monitoring of equipment load levels, self-test data and utility power conditions via built-in RS-232 and USB interfaces

HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X

Optional SNMPWEBCARD offers communications and control via secure remote web and network interfaces

Optional RELAYIOCARD supports six configurable hard contact closure outputs for custom event notification

Optional RELAYIOMINI interface module offers three configurable hard contact closure outputs for custom event notification (requires

removal of USB interface module)

Supports Emergency Power Off (EPO) via built-in interface

Included rail kit supports 9U 19 inch rackmount installation in 4 post racks

Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks

Front panel LEDs and LCD readout with scroll controls and password option supports visual monitoring of all major UPS functions and

advanced UPS settings for charge level, nominal voltage selection, frequency conversion and other operational parameters

LED / LCD display panel rotates for viewing in rackmount or tower configurations

Network-grade AC surge and noise suppression

Industrial mode option (factory preset) enables supports high current startup loads by momentarily switching to bypass mode in response to

short duration overload conditions

Frequency conversion mode enables conversion of 60Hz to 50Hz or 50Hz to 60Hz (no de-rating)

External battery packs are field replaceable and hot swappable

Specifications

OUTPUT

Output Volt Amp
Capacity (VA)

10000

Output kVA capacity
(kVA)

10

Output Watt
Capacity (watts)

9000

Output kW capacity

9.0

Output power factor

0.9

Output Capacity
Details

Supports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30
seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power;
Double conversion mode is automatically restored as load levels are reduced to 95% or less

Nominal Output
Voltage(s) Supported

120V; 208V; 240V

Frequency
compatibility

50/60 Hz (auto-selectable)

Frequency
compatibility details

Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to
50Hz or 50Hz to 60Hz; Output frequency regu/- 0.05Hz (free running)

Output voltage
regulation (line
mode)

+/- 2%

Summary of Contents for SmartOnline SU10KRT3U

Page 1: ...advanced networking applications in data centers computer rooms network closets and rugged industrial locations Package Includes SU10000RT3UPM 3U UPS power module BP240V10RT3U external battery pack SU...

Page 2: ...e offers three configurable hard contact closure outputs for custom event notification requires removal of USB interface module Supports Emergency Power Off EPO via built in interface Included rail ki...

Page 3: ...with optional external battery packs External battery pack compatibility BP240V10RT3U BP240V557C 1PH BP240V787C 1PH BP240V1037C 1PH BP240V1407C 1PH DC system voltage VDC 240 Battery recharge rate inc...

Page 4: ...neous EMI RFI AC noise suppression Yes PHYSICAL Installation form factors supported with included accessories 4 post 19 inch rackmount mounting rail kit included Tower Included mounting accessory desc...

Page 5: ...lbs 158 7 Included battery pack weight kg 72 UPS Shipping dimensions height x width x depth inches 48 25 x 40 x 48 UPS Shipping dimensions height x width x depth cm 122 6 x 101 6 x 121 9 Shipping wei...

Page 6: ...nt 100V High voltage transfer to battery power setpoint 300V SPECIAL FEATURES Cold Start startup in battery mode during a power failure Cold start operation supported Economy mode operation Optional e...

Page 7: ...LAYIOCARD Programmable Relay I O Card 1 MODBUSCARD For remote monitoring and control via MODBUS protocol 1 BP240V557C 1PH External battery pack for use with select Tripp Lite UPS Systems 1 BP240V787C...

Reviews: