AC Input
Battery
Output
Grounding Terminals
R
R
S
S
T
T
N
N
N
+
–
12
6 – Wiring
(continued)
Battery and Circuit Breaker Diagram shown for illustration only; consult the battery cabinet’s documentation for exact specifications.
Notes:
•
All internal wiring is UL-listed, MTW, 125C Hi-Flex cable.
•
Terminal block is UL-recognized and rated for 600 VDC.
•
Breaker is UL-listed and rated for 250 A, 600 VDC, 25 KAIC.
•
Cabinets with breakers are shipped with the breaker in the off/open position.
•
Battery arrangements shown are typical but may vary depending on cabinet and battery type.
6-3 UPS System Terminal Block Diagram
6-4 External Battery Cabinet Wiring Diagrams