1
5
9
3
7
11
2
6
10
4
8
12
13
14
56
12 – Specifications
12-1 UPS System Technical Specifications
12-2 UPS System Floor Loading Table
Capacity
120KVA/96KW
Input
Rating Voltage
V
220/380, 230/400, 240/415
(3
Φ
4W+PE)
Voltage Regulation
%
<70% Full Load: -48/+20 (at 230/400V); Full load: -25/+20 (230/400V)
Input Current Harmonic Distortion (Full
Load)
%
< 4
PFC (Full Load)
> 0.99
Frequency
Hz
50 / 60
Frequency Tolerance
Hz
45 ~ 65
Output
Output Voltage
V
220/380, 230/400, 240/415 (3
Φ
4W+Earth)
Output Frequency
Hz
50 / 60
Total Harmonic (Linear Load)
%
≦
3
Voltage Regulation
Static
%
±1
Dynamic
%
7 (Max Deviation for 10% ~ 90% Linear Load)
Frequency Regulation Interior Oscillator Hz
±0.05
Synchronized
%
±5
Overload
≦
125%: 10 minutes ;
≦
150%: 1minute
Audible Warning
Battery Backup
Intermittent
UPS Abnormal
Continuous
Display
LED
UPS status: Normal, Bypass, Backup and Fault
LCD
Input/Output, Bypass, Inverter, Frequency, Loading and Battery voltage, current,
UPS abnormal message and intelligent self diagnostics
Remote
Monitor
Monitor up to 31 PCs, Graphically display records and historical data and
Fault records retrieved
Control
Remote control the Inverter and alarm, setup password and auto-dial warning
Interface
Standard
RS232, Dry Contact Output/Input
Optional
SNMP card, Modbus card, Relay I/O control card, Environmental sensor box,
SNMP+5 Ports Hub
Others
Parallel Configuration
Up to 4 UPS systems of the same capacity for redundancy capacity
EPO
Standard (Local and Remote)
SRAM Event Log
Yes (500 records)
Parameter Configuration
Yes
Hot Standby Installation
Feasible
Battery Temperature Compensation
Optional
Battery Cold Start
Standard
Overall
Efficiency (at full load)
Normal
%
94
ECO
%
97
Transfer Time
ms
0
Operating Temperature
°C
0
~
40
Humidity (Non-Condensing)
%
90
Noise (@ 1 m)
dBA
≤
70
Dimension
Width
mm
520
Depth
mm
975
Height
mm
1695
Weight
Kg
379
Model SU120KX
Weight
379 kg
Floor Loading
748 kg/m²
12-212-93-3141.indb 56