background image

VOLTAGE REGULATION

Voltage regulation
description

Online, double-conversion power conditioning

Overvoltage
correction

2% output voltage regulation during overvoltages to 150

Undervoltage
correction

2% output voltage regulation during undervoltages to 80

Severe undervoltage
correction

2% output voltage regulation during undervoltages to 65 (under 70% load only)

LEDS ALARMS & SWITCHES

LED Indicators

14 LEDs indicate line power, online mode, economy/bypass mode, on-battery, overload, battery low, replace battery
and fault status information; 4-LED meter displays load and battery charge levels; LED panel rotates for viewing in
rack/tower formats

Alarms

Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions

Alarm cancel
operation

Power-fail alarm can be silenced using alarm-cancel switch

Switches

2 switches control off/on power status and alarm-cancel/self-test operation

SURGE / NOISE SUPPRESSION

UPS AC suppression
joule rating

600

UPS AC suppression
response time

Instantaneous

UPS Dataline
suppression

1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet

EMI / RFI AC noise
suppression

Yes

PHYSICAL

Installation form
factors supported
with included
accessories

4 post 19 inch rackmount (mounting rail kit included)

Installation form
factors supported
with optional
accessories

2 post rackmount (2POSTRMKITWM); Wallmount (2POSTRMKITWM); Tower (2-9USTAND)

Primary form factor

Rackmount

UPS / Power Module
dimensions in
primary form factor
(height x width x
depth / inches)

3.5 x 17.5 x 19

UPS / Power Module
dimensions in
primary form factor
(height x width x
depth / cm)

8.9 x 44.4 x 48.3

Installed whole
system total rack
space height (rack
spaces)

2U

Secondary form factor

Tower (requires 

2-9USTAND

)

Summary of Contents for SmartOnline SU1500RTXL2Ua

Page 1: ...communications via USB port DB9 serial port and SNMPWEBCARD slot Built in DB9 port offers both enhanced RS 232 enabled monitoring data plus contact closure monitoring ability HID compliant USB interf...

Page 2: ...nagement and auto shutdown features of Windows and Mac OS X Included PowerAlert UPS monitoring software supports safe unattended shutdown monitoring and control via local connected servers plus any nu...

Page 3: ...put circuit breaker 20A UPS Input cord length ft 10 UPS Input cord length m 3 Recommended Electrical Service 15A 120V BATTERY Full load runtime minutes 5 min 1200w Half load runtime minutes 14 min 600...

Page 4: ...cancel operation Power fail alarm can be silenced using alarm cancel switch Switches 2 switches control off on power status and alarm cancel self test operation SURGE NOISE SUPPRESSION UPS AC suppress...

Page 5: ...4 Battery mode BTU hr full load 664 2 AC economy mode efficiency rating 100 load 94 COMMUNICATIONS Communications interface USB HID enabled DB9 Serial Contact closure EPO emergency power off Slot for...

Page 6: ...ibution PDUB15 Dual source Power Distribution Unit PDU with Manual Transfer Switch enables Hot swappable UPS Replacement in Critical Network Applications 1 Power Distribution PDUMH15AT Metered PDU wit...

Page 7: ...ation including related products owner s manuals and additional technical specifications can be found online at www tripplite com en products model cfm txtModelID 2949 Copyright 2012 Tripp Lite All ri...

Reviews: