background image

Low voltage transfer
to battery power
(setpoint)

80V (100% load), 65V ( 

High voltage transfer
to battery power
(setpoint)

150

SPECIAL FEATURES

Cold Start (startup in
battery mode during
a power failure)

Cold-start operation supported

High availability UPS
features

Automatic inverter bypass; Hot swappable batteries

Green & high
efficiency features

High efficiency economy mode operation; Individually controllable load banks; Schedulable daily hours of economy
mode operation

CERTIFICATIONS

UPS Certifications

Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)

WARRANTY

Product Warranty
Period (Worldwide)

2-year limited warranty

Connected
Equipment Insurance
(U.S., Canada &
Puerto Rico)

$250,000 

Ultimate Lifetime Insurance

Related Items

Optional Products

Product Type

Related Model

Description

Qty.

Extended Warranties

WEXT3-2200-3000

3-Year Extended Warranty - For Smart Line-Interactive and Online
Tower or Rack models, 2200-3000VA 

1

Extended Warranties

WEXT5-2200-3000

5-Year Extended Warranty - For Smart Line-Interactive and Online
Tower or Rack models, 2200-3000VA or less 

1

External Battery Packs

BP72V15-2U

BP72V15-2U - External Battery Pack for UPS System 

1

External Battery Packs

BP72V28RT-3U

BP72V28RT-3U - External Battery Pack for UPS System 

1

Power Cables

P043-002

2-ft. 10AWG Heavy Duty Power Cord with 20 AMP Breaker, (NEMA
L5-30P to NEMA L5-20R) 

1

Power Distribution

P044-06I

6-inch 12AWG Heavy Duty Power Adapter cord
(NEMA-L5-20R to NEMA-5-20P) 

1

Power Distribution

P049-010

10-ft. 12AWG Heavy Duty Power cord
(IEC-320-C19 to NEMA 5-20P) 

1

Power Distribution

PDU2430

Basic PDU / Power Distribution Unit - Safe, reliable power distribution
for critical networking equipment 

1

Power Distribution

PDUB30

Dual source Power Distribution Unit / PDU with Manual Transfer Switch
enables Hot-swappable UPS Replacement in Critical Network
Applications 

1

Power Distribution

PDUMH30NET

Switched, Metered PDU with Remote Monitoring - 2U Rackmount
Power Distribution Unit for Networks with Individually Switchable
Outlets, Current Metering, Remote Monitoring and Control 

1

Power Distribution

PDUMNV30

Monitored PDU / Power Distribution Unit supports real-time remote
monitoring of load level, voltage and frequency with options for remote
environmental and security monitoring 

1

Summary of Contents for SmartOnline SU3000RTXL3U

Page 1: ...terfaces support simultaneous communications via USB port DB9 serial port and SNMPWEBCARD slot Built in DB9 port offers both enhanced RS 232 enabled monitoring data plus contact closure monitoring ability HID compliant USB interface enables integration with built in power management and auto shutdown features of Windows and Mac OS X Supports simultaneous detailed monitoring of equipment load level...

Page 2: ...ilt in power management and auto shutdown features of Windows and Mac OS X Included PowerAlert UPS monitoring software supports safe unattended shutdown monitoring and control via local connected servers plus any number of additional servers over IP UPS interface supports on battery low battery power restored AC voltage DC voltage output current monitoring battery charge current battery capacity A...

Page 3: ... maximum load 24A Nominal Input Voltage s Supported 110V AC 120V AC UPS input connection type L5 30P Input circuit breaker 40A UPS Input cord length ft 10 UPS Input cord length m 3 Recommended Electrical Service 30A 120V BATTERY Full load runtime minutes 5 min 2400w Half load runtime minutes 14 min 1200w Expandable battery runtime Supports extended runtime with optional external battery packs Exte...

Page 4: ...ow battery overload UPS fault and remote shutdown conditions Alarm cancel operation Power fail alarm can be silenced using alarm cancel switch Switches 2 switches control off on power status and alarm cancel self test operation SURGE NOISE SUPPRESSION UPS AC suppression joule rating 510 UPS AC suppression response time Instantaneous UPS Dataline suppression 1 line TEL DSL 1 in 1 out 10 100Base T E...

Page 5: ...elsius Relative Humidity 0 to 95 non condensing AC mode BTU hr full load 1112 7 AC economy mode BTU hr full load 520 9 Battery mode BTU hr full load 1219 3 AC economy mode efficiency rating 100 load 94 COMMUNICATIONS Communications interface USB HID enabled DB9 Serial Contact closure EPO emergency power off Slot for SNMP Web interface Network monitoring port description Supports detailed monitorin...

Page 6: ...ractive and Online Tower or Rack models 2200 3000VA or less 1 External Battery Packs BP72V15 2U BP72V15 2U External Battery Pack for UPS System 1 External Battery Packs BP72V28RT 3U BP72V28RT 3U External Battery Pack for UPS System 1 Power Cables P043 002 2 ft 10AWG Heavy Duty Power Cord with 20 AMP Breaker NEMA L5 30P to NEMA L5 20R 1 Power Distribution P044 06I 6 inch 12AWG Heavy Duty Power Adap...

Page 7: ...ors temperature humidity and contact closure inputs Requires SNMPWEBCARD or switched PDU 1 SNMP Accessories SNMPWEBCARD For remote monitoring and control via SNMP Web or Telnet 1 Tower Stands 2 9USTAND Enables Tower Placement of Rackmount UPS Systems 1 UPS Accessories MODBUSCARD For remote monitoring and control via MODBUS protocol 1 UPS Accessories RELAYIOCARD Programmable Relay I O Card 1 More i...