background image

Removes harmonic distortion, electrical impulses, frequency variations and other hard to solve power problems

Accepts input voltages between 160 and 275 (130 to 275 at loads under 70%), regulating output to selectable 200/208/220/230/240V +/-2%

3000VA/2400 watt power capacity with 8 total outlets (6 NEMA6-15/20R & 2 NEMAL6-20R) 

Standard internal battery set provides 14 minutes runtime at half load

Expandable runtime with multiple external battery packs (part# BP72V15-2U limit 1/BP72V28-3U multi-pack compatible)

Innovative design makes unit adaptable for rackmount, tower, or stacking applications 

Uses only 3 rack spaces (3U) in standard 19 inch rack

DB9 serial port for network interface; SNMP compatible

Slot for optional SNMP/web card (part# SNMPWEBCARD) 

PowerAlert unattended shutdown software and 6 ft. network cable included 

Compatible with Tripp Lite's Watchdog Service Monitoring/Reboot Software

Fault tolerant auto-bypass maintians continuous utility output to connected equipment, even in cases where the UPS is overloaded or

suffers an internal failure that requires service

Diagnostic LEDs 

Battery replacement door 

Mounting hardware included for 4 post rack enclosures, 2 post telecom rack compatible with separate purchase 2POSTRMKITWM

accessory

$250,000 Ultimate Lifetime 

connected equipment insurance

2 year manufacturer's product warranty 

Specifications

SYSTEM OVERVIEW

Voltage
compatibility

208V AC

Frequency
compatibility

50/60 Hz compatible

OUTPUT

Output VA

3000

Output watts

2400

Output nominal
voltage

208V AC (200/220/230/240V)

Output voltage
regulation

Maintains full-time sine wave output within 2% of selected nominal voltage, less than 5% total harmonic distortion

Output frequency
regulation

Regulates line frequency to 50/60Hz +/- 0.05Hz

Outlet quantity /
type

6 NEMA 6-15/20R, 2 NEMA L6-20R

Customized load
management
receptacles

2 individually controllable load banks support load shedding and remote reboot on demand of locked network devices.
Controllable via PowerAlert software to switch off optional loads, like monitors, to increase available runtime for servers
and other critical devices. (Bank A consists of 4 outlets / Bank B consists of 2 outlets)

Overload protection

Via 25A input breaker

INPUT

Maximum input
amps

14.9 / 14.3 / 13.1 / 12.6 / 12.1 Amps (depending on voltage) / 2844 watts

Input connection
type

NEMA L6-20P

Input cord length

10 ft. 14 gauge

Recommended
Electrical Service

15A 200-240V

BATTERY

Full load runtime

Internal batteries — 5 min. (3000VA)

Half load runtime

Internal batteries — 14 min. (1500VA)

Reviews: