Model #: SU3000RTXLCD3U

SmartOnline 3kVA On-Line Double-Conversion UPS, 3U Rackmount, Interactive LCD display,
100/110/120/127V NEMA outlets

 

Highlights

3000VA / 3kVA / 2700W on-line double-conversion 3U rackmount UPS

100/110/120/127V 50/60Hz output; High efficiency economy mode option

Interactive LCD with 9 selectable screens of UPS and site power data 

Expandable runtime, Hot-swap batteries, 26 in / 66cm depth

USB, RS232 & EPO ports, support for SNMP/WEB card option

2 independently switched load banks

NEMA L5-30P input; 4 NEMA 5-15R, 4 5-15/20R & 1 L5-30R outlets 

Description

 Tripp Lite Smart Online UPS systems offer high performance power protection ideal for critical server and network equipment in datacenters,
computer rooms and network closets. Online, double-conversion Uninterruptible Power Supply (UPS) maintains perfectly regulated output power by
continuously converting raw AC input to DC, then re-converting output back to AC. Fully regulated sine wave AC output with +/-2% voltage regulation
powers network equipment continuously, even during severe brownouts and overvoltages, all without depleting UPS battery reserves. Maintains
battery-derived AC output during power failures with zero transfer time. Extended runtime options available. Interactive LCD interface reports UPS
operating mode, detailed UPS and site-power data, plus enables a variety of UPS setup and configuration options. Highly efficient operation in
optional economy mode saves BTU heat output and energy costs. Network management interfaces support communications via USB, RS-232,
contact-closure and optional SNMPWEBCARD network interface. Built-in DB9 port offers both enhanced RS-232 data and basic contact closure
monitoring ability. HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and
Mac OS X. Includes PowerAlert monitoring software and complete cabling. Emergency Power Off (EPO) interface. LED display reports UPS
operating mode, line power availability, battery mode operation, inverter operation, ECO mode status and output power availability. Audible alarm
with push-button momentary alarm-cancel and silent-mode LCD configuration options. Programmable self-test. Battery independent restart.
Fault-tolerant auto-bypass mode. Field-replaceable, hot-swappable internal batteries and external battery packs. 

Package Includes

SU3000RTXLCD3U UPS System

PowerAlert Software with USB, Serial & EPO cabling

4 post rackmount installation kit

Instruction manual 

Features

Tripp Lite SU3000RTXLCD3U 3000VA / 3kVA / 2700W on-line, double-conversion 3U rackmount UPS

Selectable 100/110/120/127V output (120V factory preset) 

NEMA L5-30P input, 4 NEMA 5-15/20R, 4 5-15R & 1 L5-30R outlets

Two switched 4-outlet load banks support remote reboot or programmable load shedding options

Supports 2% output voltage regulation and zero transfer time in double conversion mode

Economy mode option offers enhanced efficiency, reduced power consumption and lower BTU emissions

11 minutes runtime at 50% load (1350W) and 4 minutes at 100% load (2700W) with internal batteries

BP72V15-2U (limit 1) or BP72V28RT3U (no limit) external battery packs available (some configurations require Tripp Lite's 

External Battery

Configuration Software

)

LCD interface reports operating mode plus 9 selectable screens of UPS data (Load percentage, kW & kVA, Power factor, Input voltage &

frequency, Output voltage & frequency, Battery voltage and charge percentage, Minutes runtime, Capacity remaining and Kw/hr.

consumption)

LCD interface also supports 16 screens of UPS configuration and setup options

Summary of Contents for SmartOnline SU3000RTXLCD3U

Page 1: ...rs both enhanced RS 232 data and basic contact closure monitoring ability HID compliant USB interface enables integration with built in power management and auto shutdown features of Windows and Mac O...

Page 2: ...127 120V 2700 watts 115V 2430 watts 110V 2295 watts 100V 2160 watts FREQUENCY REGULATION CONVERSION MODE Maximum output ratings are reduced in frequency regulation conversion mode 127 120V 1890 watts...

Page 3: ...Electrical Service 30A 120V BATTERY Full load runtime minutes 4 min 2700w Half load runtime minutes 11 min 1350w Expandable battery runtime Extended runtime supported via optional external battery pac...

Page 4: ...ting mode alarm function and a variety of additional options Alarms Audible alarm indicates UPS startup power failure low battery overload UPS fault and remote shutdown conditions Alarm cancel operati...

Page 5: ...it 0 to 40 degrees Celsius Storage Temperature Range 5 to 122 degrees Fahrenheit 15 to 50 degrees Celsius Relative Humidity 0 to 95 non condensing AC mode BTU hr full load 1025 AC economy mode BTU hr...

Page 6: ...mode operation CERTIFICATIONS UPS Certifications Tested to UL1778 USA Tested to CSA Canada Meets FCC Part 15 Category A EMI ROHS Restriction of Hazardous Substances WARRANTY Product Warranty Period Wo...

Page 7: ...lug 1 PDUMH30NET Single Phase Switched PDU 30A 120V 2U Horizontal Rackmount NEMA 5 15 20R outlets NEMA L5 30P input plug 1 PDUMNV30 Single Phase Monitored PDU 30A 120V 0U Vertical Rackmount NEMA 5 15...

Reviews: