background image

4 post installation hardware included, Optional 2POSTRMKITHD enables 2 post rack installation

Single line TEL / Network surge suppression

Electronic bypass maintains utility output during a variety of UPS fault conditions

Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries

are expired and require replacement

Frequency regulation / conversion mode offers generator-compatible frequency correction or conversion of frequency from 50 to 60Hz or 60

to 50Hz

Built-in USB, RS-232, contact-closure and optional SNMPWEBCARD accessory monitoring options

HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X

Included PowerAlert UPS monitoring software

Specifications

OUTPUT

Output Volt Amp
Capacity (VA)

3000

Output kVA
capacity (kVA)

3

Output Watt
Capacity (watts)

2700

Output kW capacity

2.7

Output power
factor

0.9

Output Capacity
Details

ON LINE MODE: Maximum output capacity ratings are reduced for some nominal voltage settings (127/120V 2700
watts / 115V 2430 watts / 110V 2295 watts / 100V 2160 watts). FREQUENCY REGULATION / CONVERSION MODE:
Maximum output ratings are reduced in frequency regulation / conversion mode (127/120V 1890 watts / 115V 1701
watts / 110V 1606 watts / 100V 1512 watts).

Crest Factor

3:1

Nominal Output
Voltage(s)
Supported

100V; 110V; 115V; 120V; 127V

Nominal Voltage
details

120V factory-default nominal voltage

Frequency
compatibility

50/60 Hz (auto-selectable); Supports 50 to 60 Hz and 60 to 50 Hz conversion

Frequency
compatibility
details

ON LINE MODE: Output frequency is automatically configured to match nominal input frequency on startup; Output
matches input frequency when +/-5Hz of nominal; Output is regulated to +/-0.05Hz when input frequency exceeds
+/-5Hz of nominal. UPS switches to battery mode when input frequency is below 40Hz or above 70Hz. FREQUENCY
REGULATION / CONVERSION MODE: Output is regulated to +/-0.05Hz of selected output frequency input is 40 to
70Hz; UPS switches to battery mode when input frequency is below 40Hz or above 70Hz. BATTERY MODE: Output is
regulated to +/-0.05Hz.

Output voltage
regulation (line
mode)

+/- 2%

Output voltage
regulation
(Economy line
mode)

+/- 10%

Output voltage
regulation (Battery
mode)

+/- 3%

Built-in UPS
output receptacles

4 5-15R outlet(s); 4 5-15/20R outlet(s); 1 L5-30R outlet(s)

Summary of Contents for SmartOnline SU3000RTXLCD3U

Page 1: ...rs both enhanced RS 232 data and basic contact closure monitoring ability HID compliant USB interface enables integration with built in power management and auto shutdown features of Windows and Mac O...

Page 2: ...127 120V 2700 watts 115V 2430 watts 110V 2295 watts 100V 2160 watts FREQUENCY REGULATION CONVERSION MODE Maximum output ratings are reduced in frequency regulation conversion mode 127 120V 1890 watts...

Page 3: ...Electrical Service 30A 120V BATTERY Full load runtime minutes 4 min 2700w Half load runtime minutes 11 min 1350w Expandable battery runtime Extended runtime supported via optional external battery pac...

Page 4: ...ting mode alarm function and a variety of additional options Alarms Audible alarm indicates UPS startup power failure low battery overload UPS fault and remote shutdown conditions Alarm cancel operati...

Page 5: ...it 0 to 40 degrees Celsius Storage Temperature Range 5 to 122 degrees Fahrenheit 15 to 50 degrees Celsius Relative Humidity 0 to 95 non condensing AC mode BTU hr full load 1025 AC economy mode BTU hr...

Page 6: ...mode operation CERTIFICATIONS UPS Certifications Tested to UL1778 USA Tested to CSA Canada Meets FCC Part 15 Category A EMI ROHS Restriction of Hazardous Substances WARRANTY Product Warranty Period Wo...

Page 7: ...lug 1 PDUMH30NET Single Phase Switched PDU 30A 120V 2U Horizontal Rackmount NEMA 5 15 20R outlets NEMA L5 30P input plug 1 PDUMNV30 Single Phase Monitored PDU 30A 120V 0U Vertical Rackmount NEMA 5 15...

Reviews: