Battery
replacement
description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage regulation
description
Online, double-conversion power conditioning maintains 2% output voltage regulation during brownouts and
overvoltages
Overvoltage
correction
Corrects overvoltages to 150V (0-100% load)
Undervoltage
correction
Corrects undervoltages to 100V at full load (90V at 100V nominal)
Severe
undervoltage
correction
Corrects brownouts to 70V (70% load) & 55V (33% load)
LEDS ALARMS & SWITCHES
LED Indicators
7 front panel LEDs indicate line power availability, AC to DC conversion, battery mode operation, inverter mode, eco
mode operation, bypass mode operation and AC output status
Front panel LCD
display
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data,
plus configuration of voltage, frequency, operating mode, alarm function and a variety of additional options
Alarms
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
Alarm cancel
operation
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option
available
Switches
2 switches control off/on power status and alarm-cancel operation; 2 additional scroll-down and scroll-up / select
options enable LCD status viewing and configuration options
SURGE / NOISE SUPPRESSION
UPS AC
suppression joule
rating
570
UPS AC
suppression
response time
Instantaneous
UPS Dataline
suppression
1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet
EMI / RFI AC noise
suppression
Yes
PHYSICAL
Installation form
factors supported
with included
accessories
4 post 19 inch rackmount (mounting rail kit included)
Installation form
factors supported
with optional
accessories
2 post rackmount (2POSTRMKITHD)
Primary form factor
Rackmount
UPS / Power
Module
dimensions in
primary form
factor (height x
width x depth /
inches)
5.2 x 17.5 x 26