background image

Highly efficient operation in optional economy mode setting, saving BTU heat output and energy costs

Internal battery set offers 30 minutes runtime at half load (1200W) and 12 minutes at full load (2400W)

Optional BP72V15-2U (limit 1), BP72V28RT-3U (multi-pack compatible) and BP72V18-2US (multi-pack compatible) external battery packs

Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual)

Compact rackmount form factor installs using only 3 rack spaces (3U) with a maximum installed depth of 26 inches

Ships with all mounting accessories for 4 post rackmount installation

Optional 2POSTRMKITHD enables 2 post rackmount installation

Optional 2-9USTAND accessory enables small-footprint upright tower placement

Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions

Network interfaces support simultaneous communications via built-in USB, DB9 serial/contact-closure and SNMPWEBCARD slot

HID compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X

Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus any number

of additional servers over IP

UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery

capacity, AC line frequency, timed inverter shutoff, activate self-test, load bank output power control and remote reboot, UPS nominal voltage adjustment

and UPS line to battery power voltage setpoints

Built-in Emergency Power Off (EPO) interface with cable

Hardwire 120V AC input/output (L-N-G)

Front panel LEDs offer current monitoring and battery charge level information

Single line TEL/DSL or network ethernet line surge suppression

$250,000 Ultimate Lifetime Insurance

Specifications

OUTPUT

Output Volt Amp Capacity (VA)

3000

Output kVA capacity (kVA)

3

Output Watt Capacity (watts)

2400

Output kW capacity

2.4

Output power factor

0.8

Crest Factor

3:1

Nominal Output Voltage(s)
Supported

110V; 120V

Nominal Voltage details

120V default

Frequency compatibility

50 / 60 Hz

Frequency compatibility details

Output frequency matches input nominal on startup, defaults to 60 Hz on cold-start

Output voltage regulation (line mode)

+/- 2%

Output voltage regulation (Economy
line mode)

+/- 10%

Output voltage regulation (Battery
mode)

+/- 2%

2 / 6 

 