background image

Frequency
compatibility

60 Hz

Frequency
compatibility details

Output frequency regu/- 0.05Hz (free running)

Output voltage
regulation (line mode)

+/- 2%

Output voltage
regulation (Economy
line mode)

+/- 10%

Output voltage
regulation (Battery
mode)

+/- 2%

Built-in UPS output
receptacles

12 5-15/20R outlet(s); 2 L6-20R outlet(s); 2 L6-30R outlet(s)

Output circuit breaker

High voltage 20A breaker protects L6-20R outlets, L6-30R outlets are unbreakered; Low voltage 20A breakers
protect 3 5-15/20R outlets each

Output AC waveform
(AC mode)

Pure sine wave

Output AC waveform
(battery mode)

Pure Sine wave

INPUT

Rated input current (at
maximum load)

24A (208V)

Nominal Input
Voltage(s) Supported

208V AC

UPS input connection
type

L6-30P

UPS Input cord length
(ft.)

10

UPS Input cord length
(m)

3

Recommended
Electrical Service

30A

BATTERY

Full load runtime
(minutes)

3.5 minutes (4500w)

Half load runtime
(minutes)

11 minutes (2250w)

Expandable battery
runtime

Supports extended runtime with optional external battery packs

External battery pack
compatibility

BP192V12-3U

DC system voltage
(VDC)

192

Battery recharge rate
(included batteries)

6 hours (from 10% to 90%)

Summary of Contents for SmartOnline SU5000RT4UTF

Page 1: ...eries are expired and require replacement Double conversion operation converts raw input from AC to DC then resynthesizes output power back to perfect sine wave AC with enhanced protection from harmon...

Page 2: ...one card based network interface option part SNMPWEBCARD or dry contact monitoring accessory part RELAYIOCARD Optional SNMPWEBCARD offers communications and control via secure remote web and network...

Page 3: ...otect 3 5 15 20R outlets each Output AC waveform AC mode Pure sine wave Output AC waveform battery mode Pure Sine wave INPUT Rated input current at maximum load 24A 208V Nominal Input Voltage s Suppor...

Page 4: ...see manual Alarms Unique audible alarms for all major UPS environmental and power conditions see manual Alarm cancel operation Alarm cancel switch Switches 2 Switches control off on power status and...

Page 5: ...Stepdown transformer weight kg 34 5 UPS Shipping dimensions height x width x depth inches 22 x 25 x 30 UPS Shipping dimensions height x width x depth cm 55 9 x 63 5 x 76 2 Shipping weight lbs 278 Shi...

Page 6: ...100V 50 load or less derates linearly High voltage transfer to battery power setpoint 280V full load 300V 90 load or less SPECIAL FEATURES Cold Start startup in battery mode during a power failure Co...

Page 7: ...arranty For SU5000RT3UHV UPS only 1 WEXT5 SU5000HV 5 Year Extended Warranty For SU5000RT3UHV UPS only 1 2POSTRMKITHD Enables 2 Post Rackmount Installation of 3U and Larger UPS Transformer and Battery...

Reviews: