background image

Replacement battery
cartridge (internal
UPS battery
replacement)

RBC5-192

 (qty 1)

Battery Access

Front panel battery access door

Battery replacement
description

Hot-swappable, user replaceable batteries

VOLTAGE REGULATION

Voltage regulation
description

Online, double-conversion power conditioning

Overvoltage correction

2% output voltage regulation during overvoltages to 280V (full load) / 300V (90% load or less)

Undervoltage
correction

2% output voltage regulation during undervoltages to 156V (full load) / 100V (50% load or less)

LEDS ALARMS & SWITCHES

LED Indicators

6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD
screen offers additional information and control options

Front panel LCD
display

Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options;
LED/LCD panel rotates for viewing in rack/tower formats (see manual)

Alarms

Unique audible alarms for all major UPS, environmental and power conditions (see manual)

Alarm cancel operation

Alarm cancel switch

Switches

2 Switches control off/on power status and alarm-cancel/self-test operation; 2 additional switches support set and
execute scrolling LCD functions

SURGE / NOISE SUPPRESSION

UPS AC suppression
response time

Instantaneous

EMI / RFI AC noise
suppression

Yes

PHYSICAL

Installation form
factors supported with
included accessories

4 post 19 inch rackmount (mounting rail kit included)

Included mounting
accessory description

2 sets of adjustable 4 post rack rails included

Installation form
factors supported with
optional accessories

2 post rackmount (2POSTRMKITWM); Tower (2-9USTAND)

Optional mounting
accessory notes

2 sets of 

2POSTRMKITHD

 required for 2 post rackmount installation of separate 4U power module and 2U

transformer

Primary form factor

Rackmount

UPS / Power Module
dimensions in primary
form factor (height x
width x depth / inches)

6.85 x 17.5 x 20.7

UPS / Power Module
dimensions in primary
form factor (height x
width x depth / cm)

17.4 x 44.5 x 52.6

Summary of Contents for SmartOnline SU5000RT4UTF

Page 1: ...eries are expired and require replacement Double conversion operation converts raw input from AC to DC then resynthesizes output power back to perfect sine wave AC with enhanced protection from harmon...

Page 2: ...one card based network interface option part SNMPWEBCARD or dry contact monitoring accessory part RELAYIOCARD Optional SNMPWEBCARD offers communications and control via secure remote web and network...

Page 3: ...otect 3 5 15 20R outlets each Output AC waveform AC mode Pure sine wave Output AC waveform battery mode Pure Sine wave INPUT Rated input current at maximum load 24A 208V Nominal Input Voltage s Suppor...

Page 4: ...see manual Alarms Unique audible alarms for all major UPS environmental and power conditions see manual Alarm cancel operation Alarm cancel switch Switches 2 Switches control off on power status and...

Page 5: ...Stepdown transformer weight kg 34 5 UPS Shipping dimensions height x width x depth inches 22 x 25 x 30 UPS Shipping dimensions height x width x depth cm 55 9 x 63 5 x 76 2 Shipping weight lbs 278 Shi...

Page 6: ...100V 50 load or less derates linearly High voltage transfer to battery power setpoint 280V full load 300V 90 load or less SPECIAL FEATURES Cold Start startup in battery mode during a power failure Co...

Page 7: ...arranty For SU5000RT3UHV UPS only 1 WEXT5 SU5000HV 5 Year Extended Warranty For SU5000RT3UHV UPS only 1 2POSTRMKITHD Enables 2 Post Rackmount Installation of 3U and Larger UPS Transformer and Battery...