background image

LEDS ALARMS & SWITCHES

LED Indicators

6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD
screen offers additional information and control options

Front panel LCD
display

Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options;
LED/LCD panel rotates for viewing in rack/tower formats; LCD Display supports ENGLISH, FRENCH, GERMAN,
ITALIAN, SPANISH and PORTUGUESE (see manual)

Alarms

Unique audible alarms for all major UPS, environmental and power conditions (see manual)

Alarm cancel
operation

Alarm cancel switch

Switches

2 Switches control off/on power status and alarm-cancel/self-test operation; 2 additional switches support set and
execute scrolling LCD functions; bundled PDU includes bypass switch to enable hot-swap UPS power module
replacement

SURGE / NOISE SUPPRESSION

UPS AC
suppression
response time

Instantaneous

EMI / RFI AC noise
suppression

Yes

ISOLATION

Output isolation
transformer

120V output is isolation transformer protected

PHYSICAL

Installation form
factors supported
with included
accessories

Tower

Included mounting
accessory
description

3 sets of adjustable 4 post rack rails included; 2-9USTAND tower kit included (supports up to 9U in tower format)

Installation form
factors supported
with optional
accessories

2 post rackmount (2POSTRMKITHD)

Optional mounting
accessory notes

3 sets of 

2POSTRMKITHD

 required for 2 post rackmount installation of separate power module, battery pack and

transformer

Primary form factor

Rackmount

UPS / Power Module
dimensions in
primary form factor
(height x width x
depth / inches)

5.14 x 17.5 x 25.82

UPS / Power Module
dimensions in
primary form factor
(height x width x
depth / cm)

13.1 x 44.4 x 65.6

Installed whole
system maximum
rack depth (inches)

32.5

Installed whole
system maximum
rack depth (cm)

82.6

Summary of Contents for SmartOnline SU8000RT3U1TF

Page 1: ...trial locations Package Includes SU8000RT3UPM 3U UPS power module BP240V10RT3U external battery pack SU5000XFMRT2U step down transformer SUPDMB710 Detachable PDU with manual bypass switch Four post compatible rack rail kit 3 sets Tower stands for upright tower configuration PowerAlert software complete data cabling and user manual Features Tripp Lite SU8000RT3U1TF 8kVA 8000VA 7200 watt on line dou...

Page 2: ...pports Emergency Power Off EPO via built in interface Included rail kit supports 8U 19 inch rackmount installation in 4 post racks Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks Optional 2 9USTAND supports upright tower placement Front panel LEDs and LCD readout with scroll controls and password option supports visual monitoring of all major UPS functions and advanced UPS sett...

Page 3: ...cription 3 wire single phase input L1 L2 G Recommended Electrical Service 208V 50A BATTERY Full load runtime minutes 5 5 min 7200w Half load runtime minutes 13 5 min 3600w Expandable battery runtime Supports extended runtime with optional external battery packs External battery pack compatibility BP240V10RT3U BP240V557C 1PH BP240V787C 1PH BP240V1037C 1PH BP240V1407C 1PH DC system voltage VDC 240 B...

Page 4: ... power module replacement SURGE NOISE SUPPRESSION UPS AC suppression response time Instantaneous EMI RFI AC noise suppression Yes ISOLATION Output isolation transformer 120V output is isolation transformer protected PHYSICAL Installation form factors supported with included accessories Tower Included mounting accessory description 3 sets of adjustable 4 post rack rails included 2 9USTAND tower kit...

Page 5: ... kg 25 9 Included battery pack dimensions height x width x depth inches 5 25 x 17 5 x 25 Included battery pack dimensions height x width x depth cm 13 3 x 44 4 x 63 5 Included battery pack weight lbs 158 7 Included battery pack weight kg 72 UPS Shipping dimensions height x width x depth inches 49 25 x 23 x 31 5 UPS Shipping dimensions height x width x depth cm 125 1 x 58 4 x 80 Shipping weight lbs...

Page 6: ...ons LINE BATTERY TRANSFER Transfer time No transfer time 0 ms in online double conversion mode Transfer time economy mode 8 ms typical power failure response in optional economy mode Low voltage transfer to battery power setpoint 100V High voltage transfer to battery power setpoint 300V SPECIAL FEATURES Cold Start startup in battery mode during a power failure Cold start operation supported Econom...

Page 7: ...A L6 20P 1 Power Cables P034 010 10 ft 14AWG Heavy Duty Power cord IEC 320 C19 to NEMA 5 15P 1 Power Cables P039 001 2 1 ft 10AWG Heavy Duty Power Splitter Cord NEMA L6 20P to 2x NEMA L6 20R 1 Power Cables P040 010 10 ft 12AWG Heavy Duty Power cord IEC 320 C19 to IEC 320 L6 20P 1 Power Cables P041 001 2 1 ft 10AWG Heavy Duty Power Splitter Cable NEMA L6 30P to 2x NEMA L6 30R 1 Power Cables P044 06...

Page 8: ...uires SNMPWEBCARD or switched PDU 1 SNMP Accessories SNMPWEBCARD For remote monitoring and control via SNMP Web or Telnet 1 UPS Accessories MODBUSCARD For remote monitoring and control via MODBUS protocol 1 UPS Accessories RELAYIOCARD Programmable Relay I O Card 1 UPS Accessories RELAYIOMINI 3 Relay I O Mini module 1 More information including related products owner s manuals and additional techni...