background image

Included battery pack weight (lbs)

158.7

Included battery pack weight (kg)

72

UPS Shipping dimensions (height x
width x depth / inches)

39.8 x 31.5 x 23

UPS Shipping dimensions (height x
width x depth / cm)

101 x 80 x 58.4

Shipping weight (lbs)

331

Shipping weight (kg)

150.3

Cooling method

Fan

UPS housing material

Steel

ENVIRONMENTAL

Operating Temperature Range

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius

Storage Temperature Range

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius

Relative Humidity

0 to 95%, non-condensing

AC mode BTU / hr. (full load)

2732

AC economy mode BTU / hr. (full
load)

1020

AC mode efficiency rating (100%
load)

91%

AC economy mode efficiency rating
(100% load)

96%

Operating Elevation (ft.)

0-3000m (0 to 10,000 ft.)

Audible Noise

60 dBA at front side 1 meter

Operating Elevation (m)

0-3000 m

COMMUNICATIONS

Communications interface

USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface

Network monitoring port description

Additional contact closure support with optional RELAYIOCARD and RELAYIOMINI interface cards. RELAYIOMINI
installation requires removal of panel containing USB ports

PowerAlert software

Included

Communications cable

USB, DB9 serial and EPO cables included

WatchDog compatibility

Supports Watchdog application, OS and hard-reboot restart options for remote applications

LINE / BATTERY TRANSFER

Transfer time

No transfer time (0 ms.) in online, double-conversion mode

Transfer time (economy mode)

8 ms. typical power failure response in optional economy mode

Low voltage transfer to battery
power (setpoint)

100V

5 / 7 

 

Summary of Contents for SmartOnline SU8000RT3UG

Page 1: ...lets Maximum installed rack depth of only 32 5 in 82 6cm inches Full time active power conditioning provides clean continuous dual conversion AC output free of voltage fluctuations power interruptions...

Page 2: ...igurable hard contact closure outputs for custom event notification requires removal of USB interface module Supports Emergency Power Off EPO via built in interface Included rail kit supports 6U 19 in...

Page 3: ...age s Supported 200V AC 208V AC 230V AC 240V AC UPS input connection type Hardwire UPS input connection description 3 wire single phase input L1 L2 G Recommended Electrical Service 50A Voltage compati...

Page 4: ...tantaneous EMI RFI AC noise suppression Yes PHYSICAL Installation form factors supported with included accessories Tower Included mounting accessory description 2 sets of adjustable 4 post rack rails...

Page 5: ...perating Elevation ft 0 3000m 0 to 10 000 ft Audible Noise 60 dBA at front side 1 meter Operating Elevation m 0 3000 m COMMUNICATIONS Communications interface USB HID enabled DB9 Serial EPO emergency...

Page 6: ...nty Period Worldwide 2 year limited warranty Related Items Optional Products Model Number Description Qty SNMPWEBCARD For remote monitoring and control via SNMP Web or Telnet 1 ENVIROSENSE Monitors te...

Page 7: ...Outlets Current Metering Remote Monitoring and Control 1 P032 007 7 ft 12AWG Heavy Duty Power cord IEC 320 C13 to IEC 320 C20 1 P036 002 2 ft 12AWG Heavy Duty Power cord IEC 320 C19 to IEC 320 C20 1...

Reviews: