9 – Display and Configuration
(continued)
9-5-4 Charger Setup
Use “ ” or ” ” to select “CHARGER”, then press ”
” to confirm.
From the “CHARGER CURRENT” screen, use the scroll buttons
(
,
) to select the desired setting and press the enter button
(
) to confirm the setting.
Note: The default charger current
setting is 7A.
Each internal power module has a 5 amp charger. Charger current
can be set from a minimum of 2 amps total to a maximum of
5 amps per internal power module, multiplied by the number
of modules.
For example, the SU80K has four internal power
modules, so its charger current range is 2-20 amps.
Set the
charger current value based on the size of the battery system. See
Section 9-5-3
for more information about determining the size of
the battery system.
Warning: Setting the charger current too high may damage
batteries and reduce their operational lifespan. Consult the
factory for guidance before changing the default setting.
Press “ ” or ” ” to change the charging current, then press
”
” to confirm.
Press “ESC” to return to the “UPS SETUP” menu.