1
5
8
3
6
10
2
9
4
7
11
12
13
55
Model (Capacity) SU80K (80kVA/64kW)
Input
Input Voltage
120/208V AC, 3Ø, 4-wire + ground
Voltage Regulation
-25% / +20%
Harmonic Distortion
< 4% (Full Load)
PFC (Full Load)
> 0.99
Frequency
50 / 60 Hz
Frequency Tolerance
45 ~ 65 Hz
Output
Output Voltage
120/208V AC, 3Ø, 4-wire + ground
Output Frequency
50 / 60 Hz
Total Harmonic (Linear Load)
≤
3%
Voltage Regulation
Static
±1%
Dynamic
±7% (10% ~ 90% Linear Load)
Frequency Regulation
Interior Oscillator ±0.05 Hz
Synchronized
±5%
Overload
≤
125% : 10 minutes;
≤
150% : 1 minute
Audible Warning
Battery Backup
Intermittent
UPS Abnormal
Continuous
Display
LED
UPS Status: Normal • Bypass • Backup • Fault
LCD
Input/Output • Bypass • Inverter • Frequency • Loading • Battery Voltage
UPS abnormal messages with intelligent self-diagnosis.
Interface
Standard
RS-232, Dry Contact
Optional
SNMPWEBCARD
Others
Parallel Redundancy
Yes (1+1 for 2 UPS systems of the same type and capacity only.)
EPO
Standard (Local and Remote)
SRAM Event Log
500 Records
Parameter Configuration
Yes
Hot Standby Installation
Optional
Battery Temperature Compensation
Optional
Battery Cold-Start
Standard
Overall
Efficiency
Normal
92%
ECO
96%
Transfer Time
0 ms
Temperature
32° F ~ 104° F (0° C ~ 40° C)
Humidity (non-condensing)
90%
Noise (1 m)
70 dBA
Dimensions (Power Module) Width
20.47 in (520 mm)
Depth
40.39 in (1026 mm)
Height
66.77 in (1696 mm)
Weight (Power Module)
1,444 lb (655 kg)
11 – Specifications
11-1 UPS System Technical Specifications
11-2 UPS System Floor Loading Table
11-3 Battery Pack Floor Loading Table
BP480V26B
BP480V40C
(40 12V batteries;
(40 12V batteries;
Model
26AH each)
40AH each)
Weight
1,036 lb (470 kg)
1,543 lb (700 kg)
Floor Loading
1064 kg/m
2
1575 kg/m
2
Model
SU80K
Weight
1,444 lb (655 kg)
Floor Loading
1228 kg/m
2