Specifications
Storage & Service
Storage
First turn your UPS OFF and disconnect its power cord from the wall outlet.
Then disconnect all equipment to avoid battery drain. If you plan to store
your UPS for an extended period of time, fully recharge the UPS batteries once
every three months by plugging the UPS into a live AC outlet, turning the Power
Switch ON and letting the UPS charge for 4-6 hours. If UPS batteries remain
uncharged for an extended period of time, they will suffer permanent loss of
capacity.
Service
If returning your UPS for service, contact your local Tripp Lite dealer or
distributor. They will refer you to a service center. Please carefully pack the UPS
using the ORIGINAL PACKING MATERIAL that came with the unit. Enclose a
letter des-cribing the symptoms of the problem. If the UPS is within the 2 year
warranty period, enclose a copy of your sales receipt.
Model
SmartPro 450 RTI
Output Capacity (VA/Watts):
450/270
Battery Runtime (Half Load/Full Load) Minutes:
12/3
Typical Runtime (Desktop PC/15 in. monitor) Minutes:
20
Battery Recharge Time:
2-4 hrs.
Approvals:
CE
Input Voltage (230V); Input Frequency (50/60 Hz, Auto-Selecting); On-Line Input Voltage Range (187-280 volts); Voltage-Regulated
Output Voltage Range (230V +6%/-12%); On-Battery Output Voltage Range (230V ±5%); Output Waveform Line Mode (filtered
sinewave); Output Waveform Battery Mode (PWM sine wave); AC Surge Suppression (exceeds IEEE 587 Cat. A standards);
AC Noise Attenuation (>40 dB); AC TVSS Protection Modes (H to N, H to G, N to G).
The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change.
Wire Color
Wire 1
Wire 2
Wire 3
American
Black
White
Green
European
Brown
Blue
Green/Yellow
Wire Reference
Wire 1
Wire 2
Wire 3
American
Line 1
Neutral
Ground
European
Line 1
Line 2 or Neutral
Ground
200004074 Smart 450 RTI 230V OM.p65
4/14/00, 3:12 PM
8