8
Storage & Service
Storage
Turn your UPS OFF: first engage the ON/Standby Switch and release it to place
your UPS in the “Standby” mode, then move the System Enable Switch to the
“DISABLE” (DOWN) position to prevent battery drain, then disconnect the UPS
power cord from the wall outlet. If you plan on storing your UPS for an extended
period of time, recharge the UPS batteries once every three months. Follow
steps #3 and #4 in the Quick Installation section and allow the UPS to charge
until the “
” light glows green (may take 6 or more hours depending on the
number of batteries connected). If you leave your UPS batteries discharged for
an extended period of time, they may suffer permanent loss of capacity.
Service
If returning your UPS for service, contact your local Tripp Lite dealer or
distributor. They will refer you to a service center. Please carefully pack the UPS
using the ORIGINAL PACKING MATERIAL that came with the unit. Enclose a
letter describing the symptoms of the problem. If the UPS is within the 2 year
warranty period, enclose a copy of your sales receipt.
Specifications
SMARTDC3000INT
SMARTDC3000XRINT
Output Capacity (VA/Watts):
3000/2400
3000/2400
Battery Runtime (with Battery Pack) (with 1 BP36V33*)
(with 1 BP36VXR*)
for Half Load/Full Load in Minutes:
26+/11+
†
84+/36+
†
Battery Recharge Time:
2-4 hrs.
2-4 hrs.
Approvals:
—
—
SMARTDC5000INT
SMARTDC5000XLINT
Output Capacity (VA/Watts):
5000/3750
5000/3750
Battery Runtime (with Battery Pack) (with 1 BP36V33*)
(with 2 BP36V33*)
for Half Load/Full Load in Minutes:
42+/18+
†
108+/42+
†
Battery Recharge Time:
2-4 hrs.
2-4 hrs.
Approvals:
SASO
SASO
* Included with UPS.
† Battery Runtime can be increased by adding additional external battery packs. This will increase recharge time, however.
Input Voltage (220-240V); Input Frequency (50 Hz); On-Line Input Voltage Range (166-276 volts); Voltage-Regulated Output Voltage
Range (220/240V +8%/-15%); On-Battery Output Voltage Range (220/240V ± 5%); Output Waveform Line Mode (filtered sinewave); Output
Waveform Battery Mode (PWM sine wave); AC Surge Suppression (exceeds IEEE 587 Cat. A & B standards);
AC Noise Attenuation (>40 dB); AC TVSS Protection Modes (H to N, H to G, N to G).
The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change.