background image

Emergency Power Off (EPO) interface with cable

Multi-function audible alarms and set of 5 front panel LEDs

C14 inlet accepts user-supplied AC power cord with country specific plug

Network-grade AC surge suppression

Field-replaceable, hot-swappable internal UPS batteries

Specifications

OUTPUT

Output Volt Amp Capacity
(VA)

500

Output Watt Capacity
(watts)

300

Output power factor

0.6

Nominal Output Voltage(s)
Supported

220V; 230V; 240V

Nominal Voltage details

230v nominal inverter output voltage

Frequency compatibility

50 / 60 Hz

Output voltage regulation
(line mode)

-8%, +15%

Output voltage regulation
(Battery mode)

+/- 5%

Built-in UPS output
receptacles

6 C13 outlet(s)

Included output power
cables

Two 1.8m IEC320-C13 to C14 load jumper cables

Surge suppression only
outlets

6 UPS outlets, 1 surge-only outlets

Built-in controllable
switched load banks

One switchable single-outlet C13 load bank

Output AC waveform (AC
mode)

Sine wave

Output AC waveform
(battery mode)

PWM sine wave

INPUT

Rated input current (at
maximum load)

2.4A

Nominal Input Voltage(s)
Supported

230V AC

UPS input connection type

C14 inlet

UPS input connection
description

C14 inlet accepts user-supplied AC power cord with country-specific plug

Input circuit breaker

8A

BATTERY

Full load runtime (minutes)

3.2 min. (300w)

Half load runtime
(minutes)

14.6 min. (150w)

Summary of Contents for SmartPro Rackmount SMX500RT1U

Page 1: ...eous power off of UPS and connected equipment in the case of fire or emergency situation Multi function audible alarms and set of 5 front panel LEDs offer at a glance notification of UPS and line power status Network grade AC surge suppression protects equipment from damage and performance problems resulting from transient surges and line noise Attractive all black color scheme Package Includes SM...

Page 2: ...e mode 8 15 Output voltage regulation Battery mode 5 Built in UPS output receptacles 6 C13 outlet s Included output power cables Two 1 8m IEC320 C13 to C14 load jumper cables Surge suppression only outlets 6 UPS outlets 1 surge only outlets Built in controllable switched load banks One switchable single outlet C13 load bank Output AC waveform AC mode Sine wave Output AC waveform battery mode PWM s...

Page 3: ... operation Power fail alarm can be silenced using alarm cancel switch once silenced alarm will re sound to indicate low battery status Switches 2 Switches control off on power status and alarm cancel self test operation SURGE NOISE SUPPRESSION UPS AC suppression joule rating 480 joules EMI RFI AC noise suppression Yes PHYSICAL Installation form factors supported with included accessories 4 post 19...

Page 4: ...upports Watchdog application OS and hard reboot restart options for remote applications LINE BATTERY TRANSFER Transfer time 2 4 milliseconds Low voltage transfer to battery power setpoint 187 High voltage transfer to battery power setpoint 264 SPECIAL FEATURES Grounding lug Back panel grounding lug Cold Start startup in battery mode during a power failure Cold start operation supported High availa...

Page 5: ...r distribution for critical networking equipment 1 SNMPWEBCARD For remote monitoring and control via SNMP Web or Telnet 1 U022 010 10 ft USB2 0 A B Gold Device Cable A Male to B Male 1 WATCHDOGSW WatchDog Service Monitoring Reboot Software 1 MODBUSCARD For remote monitoring and control via MODBUS protocol 1 More information including related products owner s manuals and additional technical specif...

Reviews: