background image

Output

Input

Output Volt Amp Capacity (VA)
Output kVA Capacity (kVA) 
Output Watt Capacity (watt)
Output power factor 
Nominal output voltage(s) 
supported
Frequency compatibility 
Output voltage regulation  
(line mode)
Output voltage regulation 
(battery mode)
Built-in UPS output receptacles
Built-in controllable switched 
load banks
Output AC waveform (AC mode)

Output AC waveform (battery 
mode)

1500
1.5
980 
0.7
120V

60Hz

-18%, +8%

± 5% 
6 5-15R outlet(s)
One switchable single-outlet 

5-15R load bank
Sine Wave

PWM Sine Wave

Rated input current  
(at maximum load)
Nominal input voltage(s)
supported
UPS input connection type
Input circuit breaker 
UPS input cord length (ft) 
UPS input cord length (m)
Recommended electrical 
service
 

12A
120V AC 

5-15P
15A
6
1.8
15A, 120V

Battery

Voltage Regulation

Full load runtime (minutes) 
Half load runtime (minutes) 
DC system voltage (VDC)
Battery recharge rate

(included batteries)
Replacement battery

cartridge (internal UPS

battery replacement)
Battery access
Battery replacement 
description

7 minute (980W)
20 minute (490W)
36V DC
Less than 4 hours from  
10% to 90% 

RBC53 
Battery access door
Hot-swappable, user 
replaceable batteries

Voltage regulation 
description

Overvoltage correction

Undervoltage correction

Severe undervoltage

correction

Automatic Voltage 
Regulation (AVR) maintains 
line power operation with 
an input voltage range of 
75 to 147
Input voltages between 
128 and 147 are reduced 
by 12%

Input voltages between 93 
and 107 are boosted  
by 14% 
Input voltages between 75 
and 92 are boosted by 30%

LEDs Alarms and Switches

Surge/Noise Suppression

LED indicators 

Alarms 
 

Alarm cancel operation 

Switches

5 LEDs indicate line power, 

battery power, overload,  

voltage regulation and battery 

low/replace status
Audible alarm indicates  

power-failure, overload and 

low-battery conditions
Power-fail alarm can be silenced 

using alarm-cancel switch; once 

silenced, alarm will re-sound to 
indicate low-battery status
2 Switches control off/on power 

status and alarm-cancel/ 

self-test operation

UPS AC suppression joule 

rating
UPS AC suppression

response time
EMI/RFI AC noise 
suppression

480J
 
Instantaneous

Yes

SPECIFICATIONS

•  Includes 1 USB and 1 DB9 monitoring port for remote  
  monitoring of UPS status and site power conditions
•  Communications ports enable safe unattended shutdown  
  without data loss during extended power failures
•  Communications ports support messaging of UPS and  
  line power status, including on-battery, low-battery,  
  power-restored, AC line voltage, DC battery voltage and 
  battery capacity
•  Communications ports support timed inverter shutoff  
  after unattended shutdown, activate self-test and 10  
  second reboot of connected equipment
•  PowerAlert UPS monitoring and unattended shutdown  
  software with complete cabling included
•  Supports Tripp Lite’s WatchDog software application to 
  restore unresponsive programs by automatically restarting 
  them and rebooting completely locked computers by 
  automatically switching UPS power off and back on again

•  Notification of system status via 5 LEDs and multifunction  

 

  audible alarms
•  Wall mountable with UPSWM wallmount bracket
•  Attractive small footprint beige tower housing uses less  

 

  than 66 square inches
•  Hot-swappable/user replaceable batteries allow on-site  

 

  battery replacement
•  Cold start capability enables UPS turn-on in battery mode  

 

  during blackout conditions
•  UL (U.S.), cUL (Canada), NOM (Mexico), Class A (Emissions)
• 

$

250,000 Ultimate Lifetime Insurance (U.S. and Canada only)

•  2-year manufacturers product warranty with 

$

250,000  

 

  connected equipment insurance (U.S. and Canada only)