Input circuit breaker
20A
UPS Input cord length (ft.)
10
UPS Input cord length (m)
3
Recommended Electrical
Service
20A 120V
BATTERY
Full load runtime (minutes)
11 min. (1900w)
Half load runtime
(minutes)
28 min. (950w)
Expandable battery
runtime
Extended runtime supported via optional external battery packs
External battery pack
compatibility
BP48V24-2U
(limit 1);
BP48V48RT4U
(multi-pack compatible)
DC system voltage (VDC)
48
Battery recharge rate
(included batteries)
Less than 3.6 hours from 10% to 90%
Replacement battery
cartridge (internal UPS
battery replacement)
RBC54
(quantity 2)
Battery Access
Front panel battery access door
Battery replacement
description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage regulation
description
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145
Overvoltage correction
Input voltages between 127 and 145 are reduced by 12%
Undervoltage correction
Input voltages between 96 and 108 are boosted by 12%
Severe undervoltage
correction
Input voltages between 83 and 95 are boosted by 24%
LEDS ALARMS & SWITCHES
LED Indicators
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Alarms
Audible alarm indicates power-failure, overload and low-battery conditions
Alarm cancel operation
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate
low-battery status
Switches
2 Switches control off/on power status and alarm-cancel/self-test operation; rear panel protected switches
support low/high charger settings
SURGE / NOISE SUPPRESSION
UPS AC suppression
joule rating
570
UPS AC suppression
response time
Instantaneous
EMI / RFI AC noise
suppression
Yes
PHYSICAL