background image

2-9USTAND enables tower placement

Built-in USB, RS-232 and optional SNMPWEBCARD accessory monitoring options

HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X

Included PowerAlert UPS monitoring software; Built-in Emergency Power Off (EPO) interface with cable

Specifications

OUTPUT

Output Volt Amp
Capacity (VA)

750

Output kVA capacity
(kVA)

.75

Output Watt Capacity
(watts)

600

Output kW capacity

.6

Output power factor

0.8

Output Capacity
Details

Output derates to 450 watts in all external battery pack configurations

Nominal Output
Voltage(s) Supported

120V

Frequency
compatibility

60 Hz

Output voltage
regulation (line mode)

-21%, +8%

Output voltage
regulation (Battery
mode)

+/- 5%

Built-in UPS output
receptacles

6 5-15R outlet(s)

Built-in controllable
switched load banks

Two switchable two-outlet 5-15R load banks

Output AC waveform
(AC mode)

Sine wave

Output AC waveform
(battery mode)

Pure Sine wave

INPUT

Rated input current
(at maximum load)

7.5A

Nominal Input
Voltage(s) Supported

120V AC

UPS input
connection type

5-15P

Input circuit breaker

10A

UPS Input cord
length (ft.)

10

UPS Input cord
length (m)

3.05

Summary of Contents for SmartPro SMART750RMXL2U

Page 1: ...te cabling Switched output load banks enable scheduled and real time remote reboot and load shedding of select outlets Emergency Power Off EPO interface LCD display panel easily rotates for viewing in rackmount or tower configurations Audible alarm with push button momentary alarm cancel and silent mode configuration options Programmable self test Field replaceable hot swappable battery modules Pa...

Page 2: ...r factor 0 8 Output Capacity Details Output derates to 450 watts in all external battery pack configurations Nominal Output Voltage s Supported 120V Frequency compatibility 60 Hz Output voltage regulation line mode 21 8 Output voltage regulation Battery mode 5 Built in UPS output receptacles 6 5 15R outlet s Built in controllable switched load banks Two switchable two outlet 5 15R load banks Outpu...

Page 3: ...rvoltage correction Input voltages between 128 and 147 are reduced by 12 Undervoltage correction Input voltages between 83 and 107 are boosted by 14 LEDS ALARMS SWITCHES LED Indicators Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data plus configuration of voltage operating mode alarm function and a variety of additional options see m...

Page 4: ...ng weight kg 21 1 Cooling method Fan UPS housing material Steel ENVIRONMENTAL Operating Temperature Range 32 to 104 degrees Fahrenheit 0 to 40 degrees Celsius Storage Temperature Range 5 to 122 degrees Fahrenheit 15 to 50 degrees Celsius Relative Humidity 0 to 95 non condensing AC mode BTU hr full load 109 COMMUNICATIONS Communications interface USB DB9 Serial EPO emergency power off Slot for SNMP...

Page 5: ...rranty For Smart Line Interactive and Online Tower or Rack models 1500VA or less 1 SNMPWEBCARD For remote monitoring and control via SNMP Web or Telnet 1 ENVIROSENSE Monitors temperature humidity and contact closure inputs Requires SNMPWEBCARD or switched PDU 1 SRSWITCH Magnetic Door Switch Kit for front and rear doors requires ENVIROSENSE 1 RBC24V LCD 2U UPS Replacement Battery Cartridge for sele...

Page 6: ...ET Single Phase Switched PDU 15A 120V 1U Horizontal Rackmount 16 NEMA 5 15R outlets NEMA 5 15P input plug 1 PDUMV15NET Single Phase Switched PDU 15A 120V 0U Vertical Rackmount 16 NEMA 5 15R outlets NEMA 5 15P input plug 1 More information including related products owner s manuals and additional technical specifications can be found online at www tripplite com en products model cfm txtModelID 3020...

Reviews: