background image

WatchDog
compatibility

Supports Watchdog application, OS and hard-reboot restart options for remote applications

LINE / BATTERY TRANSFER

Transfer time

6 milliseconds (AC to battery mode), 1 millisecond (Battery to AC mode)

Low voltage transfer
to battery power
(setpoint)

158

High voltage transfer
to battery power
(setpoint)

278

SPECIAL FEATURES

Cold Start (startup in
battery mode during
a power failure)

Cold-start operation supported

High availability UPS
features

Hot swappable batteries

Green & high
efficiency features

Greater than 95% efficiency - GREEN UPS; Individually controllable load banks; Schedulable daily hours of
economy mode operation

CERTIFICATIONS

UPS Certifications

CE; ROHS (Restriction of Hazardous Substances)

UPS Certification
details

IEC 62040-1, IEC 62040-2 Class A EMI, GOST

WARRANTY

Product Warranty
Period (Worldwide)

2-year limited warranty

Related Items

Optional Products

Related Model

Description

Qty.

BP48V24-2U

External Battery Pack for UPS System 

1

BP48V60RT-3U

External Battery Pack and Cable. 3U, Expandable, Blue 2-Point Connector 

1

SNMPWEBCARD

For remote monitoring and control via SNMP, Web or Telnet 

1

ENVIROSENSE

Monitors temperature, humidity and contact-closure inputs. (Requires UPS with
SNMPWEBCARD, monitored PDU or switched PDU.) 

1

SRSWITCH

Magnetic Door Switch Kit for front and rear doors; requires ENVIROSENSE 

1

2-9USTAND

Enables Tower Placement of Rackmount UPS Systems 

1

MODBUSCARD

For remote monitoring and control via MODBUS protocol 

1

2POSTRMKITWM

Enables 2-Post Rackmount or Wallmount Installation of Select Rackmount UPS Systems 

1

RBC58-2U

2U UPS Replacement Battery Cartridge for select Tripp Lite UPS systems 

1

PDUNV

Single-Phase Basic PDU, 16A 100-240V, 1U Rackmount, C13 C19 outlets, C20 input
and C14, L6-20P, L5-20P, 5-20P and 5-15P adapters 

1

PDU12IEC

Single-Phase Basic PDU, 16A 100-240V, 1U Horizontal Rackmount, 12 C13 and 2 C19
outlets, C20 inlet 

1

PDUMH20HV

Single-Phase Metered PDU, 16/20A 200-240V, 1U Horizontal Rackmount, 2 C19 and 8
C13 outlets, C20 input with NEMA L6-20P adapter 

1

Summary of Contents for SmartPro SMX3000XLRT2UA

Page 1: ...nd auto shutdown features of Windows and Mac OS X Network communications ports enable detailed monitoring of equipment load levels self test data and utility power conditions Includes PowerAlert monitoring software and complete cabling Switched output load banks enable scheduled and real time remote reboot and load shedding of select outlets Emergency Power Off EPO interface LCD display panel easi...

Page 2: ...capacity kVA 3 Output Watt Capacity watts 2700 Output kW capacity 2 7 Output power factor 9 Nominal Output Voltage s Supported 230V Frequency compatibility 50 60 Hz Output voltage regulation line mode 6 15 Output voltage regulation Battery mode 5 Built in UPS output receptacles 8 C13 outlet s 1 C19 outlet s Included output power cables Set of 3 C13 to C14 power cables included Built in controllabl...

Page 3: ...ervoltage correction Input voltages between 206 and 183 are boosted by 12 Severe undervoltage correction Input voltages between 158 and 183 are boosted by 24 LEDS ALARMS SWITCHES Front panel LCD display Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data plus configuration of voltage operating mode alarm function and a variety of additi...

Page 4: ... inches 9 x 23 75 x 20 5 UPS Shipping dimensions height x width x depth cm 22 9 x 60 3 x 52 1 Shipping weight lbs 72 6 Shipping weight kg 33 Cooling method Fan UPS housing material Steel ENVIRONMENTAL Operating Temperature Range 32 to 104 degrees Fahrenheit 0 to 40 degrees Celsius Storage Temperature Range 5 to 122 degrees Fahrenheit 15 to 50 degrees Celsius Relative Humidity 0 to 95 non condensin...

Page 5: ...n Qty BP48V24 2U External Battery Pack for UPS System 1 BP48V60RT 3U External Battery Pack and Cable 3U Expandable Blue 2 Point Connector 1 SNMPWEBCARD For remote monitoring and control via SNMP Web or Telnet 1 ENVIROSENSE Monitors temperature humidity and contact closure inputs Requires UPS with SNMPWEBCARD monitored PDU or switched PDU 1 SRSWITCH Magnetic Door Switch Kit for front and rear doors...

Page 6: ...T2 Single Phase Switched PDU 20A 200 240V 39 in 1m 0U Vertical Rackmount 7 C13 1 C19 outlets C20 inlet and NEMA L6 20P cable 1 P004 001 1 ft 18AWG Power Cord IEC 320 C14 to IEC 320 C13 1 P004 002 2 ft 18AWG Power cord IEC 320 C14 to IEC 320 C13 1 P004 002 13A 2 ft 16AWG Power Cord IEC 320 C14 to IEC 320 C13 1 P004 002 5 5 Pack of 2 ft 18AWG Power cord IEC 320 C14 to IEC 320 C13 1 P004 003 3 ft 18A...