Replacement battery
cartridge (internal
UPS battery
replacement)
RBC53
Battery Access
Battery access door allows hot swap battery replacement without powering connected equipment off
Typical battery
lifespan
3-6 years, depending on usage
VOLTAGE REGULATION
Voltage regulation
description
Line interactive UPS offers 2 boost levels of brownout correction and a single level of overvoltage adjustment to
maintain usable, computer grade output without consuming battery power over an input voltage range of 155 to
274V AC
Overvoltage correction
Input voltages between 206 and 245V AC are reduced by 9%
Undervoltage
correction
Input voltages between 183 and 199 are boosted by 10%
Severe undervoltage
correction
Input voltages between 155 and 182 are boosted by 21%
Direct pass through
Input voltages between 200 and 244V AC are passed through unchanged
LEDS ALARMS & SWITCHES
LED Indicators
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Alarms
3 function audible alarm indicates power failure conditions (4 short beeps every 10 seconds), overload (continuous
short beeps) and low battery (continuous tone)
Switches
Yes, includes 2 front panel mounted push-button switches for system enable, self-test and alarm cancel functions
SURGE / NOISE SUPPRESSION
UPS AC suppression
joule rating
340 joules
EMI / RFI AC noise
suppression
Yes
AC suppression
response time
Instantaneous
PHYSICAL
Installation form
factors supported with
included accessories
Tower
Installation form
factors supported with
optional accessories
Wallmount (UPSWM - tower mounting kit)
UPS / Power Module
dimensions in primary
form factor (height x
width x depth / inches)
12.8 x 7.5 x 9
UPS / Power Module
dimensions in primary
form factor (height x
width x depth / cm)
32.5 x 19 x 22.9
UPS / Power Module
weight (lbs)
42.1
UPS / Power Module
weight (kg)
19.1