background image

The drawing below shows bypass utility input 

A

, UPS isolation input 

B

, and UPS isolation output 

C

 termination points.  The bypass output 

D

 is 

prewired to the distribution panel, which reduces installation time. Use 

the attached table as a wiring guideline subject to NEC and local codes.  

Flexible cable and conduit is recommended for ease of installation. 

Access panels are located on the side and rear of the bypass enclosure for 

access to termination points.

Wiring

Front View

Side View

 

 

 

 

 

Tripp Lite P/N

Voltage

DP Poles DP 

Breaker MBP

MBP 

Breaker KAIC Rating Cable Size

SUDC208V42P

208Y/120V

42

225A

 - 

 - 

10

000 AWG

SUDC208V42P30M 208Y/120V

42

225A

20 & 

30kVA

100A

18

4 AWG

SUDC208V42P40M 208Y/120V

42

225A

40kVA

150A

65

2 AWG

SUDC208V42P60M 208Y/120V

42

225A

60kVA

225A

65

000 AWG

SUDC208V84P60M 208Y/120V

84

225A

60kVA

225A

65

000 AWG

Wiring Guidelines