4T

Feature Identification

Identify the premium features on your specific model and quickly locate instructions on how to maximize their use.

Configuration DIP

Switches:

optimize UPS System

operation depending on your application. See Configuration 
section for setting instructions.

Operating Mode Switch:

controls UPS System operation. 

See Operation section for setting instructions.

“LINE”, “INVERT”, “LOAD” LEDs:

show whether the UPS

System is operating from AC line  power or DC battery power.
It also warns you if the connected equipment load is too high. See
Operation section for instructions on reading the indicator lights.

“BATT VOLT/CHRG CURR” LEDs: 

these three lights will turn

ON in several sequences to show two separate operational condi-
tions depending on the position of the Operating Mode Switch. See
Operation section for instructions on reading indicator lights.

DC Power Terminals:

connect to your battery terminals. See 

Battery Connection section for instructions.

AC Receptacles (not on hardwire models):

allow you to connect

equipment that would normally be plugged into a utility outlet. 

AC Input Cord (not on hardwire models):

connects the 

UPS System to any source of utility- or generator-supplied 
AC power. See AC Input/Output Connection section for instructions.

Hardwire AC Input/Output Terminals (not on corded 
models):

securely connect the UPS System to electrical system

input and equipment output. See AC Input/Output Connection
section for instructions.

Resettable Circuit Breaker:

protect your UPS System against

damage due to overload. See Operation section for resetting
instructions.

Main Ground Lug:

properly grounds the UPS System to

earth ground. See Configuration section for instructions.

Multi-Speed Cooling Fan:

quiet, efficient fan prolongs equipment

service life.

Hardwire AC Input/Output Cover Plate

Battery Temperature Sensing Connector (not on TMU612
models):

prolongs battery life by adjusting charge based on bat-

tery temperature. Use with included cable. See Configuration
section for details.

Low Battery Relay (not on TMU612 models):  

when battery

reaches low voltage, this relay can signal traffic controller to go
to flashing red mode or to send low battery alert to your control
center. See Configuration section for details.

Optional Features for alternate uses of Tripp Lite Traffic
MOVE-UPS

Tripp Lite’s TMU UPS models are versatile and can be used in
mobile applications as well, such as running AC power tools in
municipal maintenance trucks or police command vehicles.
The features listed below are available for such alternate uses.

Remote Control Module Connector:

designed only for mobile

applications, this connector allows remote control from up to 50
feet away with optional module, sold separately. If required,
contact Tripp Lite for further information.

Load Sense Dial (not on TMU612 models):

designed only for

mobile applications, this dial sets the low load level at which the
UPS System’s inverter automatically shuts down. To guard
against inadvertent inverter shutdown, Tripp Lite recommends
you leave the dial in its factory default setting (fully clockwise).
If required, contact Tripp Lite for further information.

1

2

3

4

5

6

7

10

HOT    IN

NEUTRAL    IN

GROUND    IN

GROUND    OUT

HOT    OUT

“FOR USE WITH COPPER WIRE ONLY”

NEUTRAL    OUT

1

2

4

3

5

9

8

Front View (Hardwire Models)

10

Rear View (Hardwire Models and Select Corded Models)

Front View (Corded Models) 

* 612 models have only one set of DIP Switches. ** Select models include front-mounted ground lug. † Available on all models except 612 models.

2

4

3

5

6

7

9

10

**

Side or Rear Mounted,
Not Shown

Side or Rear Mounted, 
Not Shown

Side Mounted, 
Not Shown

Side Mounted, 
Not Shown

11

12

13

14

15

16

11

1

*

15

16

13

14

11

15

16

13

14

12

8

9

Summary of Contents for TMU Series

Page 1: ...abinets Premium Protection for Critical Equipment Built in ISOBAR power conditioning spike surge low voltage high voltage and lightning protection Rapid recharge high amp 3 stage battery charger Rapid automatic transfer switching from line power to inverter power Automatic overload protection Relay for low battery alarm flashing red mode traffic signals Cost Effective Features for All Budgets Powe...

Page 2: ...ranty to register the warranty of your new Tripp Lite product You ll be automatically entered into a drawing for a chance to win a FREE Tripp Lite product No purchase necessary Void where prohibited Some restrictions apply See website for details Service Maintenance Service Before returning your UPS System for service follow these steps 1 Review the installation and operation instructions to ensur...

Page 3: ...application in a dead air compartment Ideally any compartment would have some ventilation to outside air Sparks may result during final battery connection Always observe proper polarity as batteries are connected Do not allow objects to contact the two DC input terminals Do not short or bridge these terminals together Serious personal injury or property damage could result Equipment Connection War...

Page 4: ... prolongs equipment service life Hardwire AC Input Output Cover Plate Battery Temperature Sensing Connector not on TMU612 models prolongs battery life by adjusting charge based on bat tery temperature Use with included cable See Configuration section for details Low Battery Relay not on TMU612 models when battery reaches low voltage this relay can signal traffic controller to go to flashing red mo...

Page 5: ...upport The light will BLINK to alert you when the inverter shuts down due to a severe overload or over heating If this happens turn the operating mode switch OFF remove the overload and let the unit cool You may then turn the operating mode switch to AUTO REMOTE after it has adequate ly cooled This light will be off when AC power is supplying the load BATT VOLT CHRG CURR LEDs If the switch is in t...

Page 6: ...el of your unit see dia gram as follows A1 A2 Most of your connected equipment will perform adequately when your UPS System s High AC Input Voltage Point DIP Switch 2 of Group A is set to 135V and its Low AC Voltage Input Point DIP Switches 3 and 4 of Group A or DIP Switch 3 for 612 models are set to 95V However if the unit frequently switches to battery power due to momentary high low line voltag...

Page 7: ... any load size Configuration continued B1 B2 B3 B4 B1 B2 B3 B4 B1 B2 B3 B4 B1 B2 B3 B4 B1 B2 B3 B4 Connect Battery Temperature Sensing Cable 1012 and 2012 models only The battery temperature sensing function prolongs battery life by adjusting the charge float voltage level based on battery temperature Connect the sensor cable the cable included with select models has an RJ style connector on one e...

Page 8: ...equate ventilation space behind the cooling fan s they should not be removed 5 87 in 14 91 cm 1 64 in 4 15 cm 5 87 in 14 91 cm 5 57 in 14 16 cm 5 57 in 14 16 cm 9 59 in 24 35 cm 9 59 in 24 35 cm 6 75 in 17 1 cm 7 87 in 20 cm 6 75 in 17 1 cm 4 5 in 11 4 cm A C B M A B M A B C A B Note Cabinets may have different front panel features but all mount as per the figure above or via the Lateral Mounting ...

Page 9: ...ow traffic managers to feel comfortable with fewer battery amp hours and shorter back up times thereby minimizing budgetary outlays for batteries auxilliary cabinets and battery maintenance STEP 1 Determine Total Wattage Required Add the wattage ratings of all equipment you will connect to your UPS System Wattage ratings are usually listed in equipment manuals or on nameplates If your equipment is...

Page 10: ...fuse s and fuse block s within 18 inches of the battery The fuse s rating must equal or exceed the Minimum DC Fuse Rating listed in your UPS System s specifications See Specifications for fuse and fuse block rec ommendations See diagrams below for proper fuse placement Battery Connection Connect your UPS System to your batteries using the following procedures WARNING Failure to properly ground you...

Page 11: ...e UPS System s AC input cord into an outlet providing 120V AC 60Hz power Make sure that the circuit you connect your UPS System to has adequate overload protection such as a circuit breaker or a fuse Plug your equipment into the UPS System s AC receptacles Any equipment you connect to it will benefit from your UPS System s built in ISOBAR power conditioning including surge spike and lightning prot...

Page 12: ...ltage Check external are slowly flashing second flashes with prevent battery damage battery connections and fuse Unit automatically resets when Operating Mode Switch in the condition is cleared AUTO REMOTE position All Three BATT VOLT CHRG CURR LEDs Battery is overcharged Unit will shut down to prevent battery Disconnect any auxiliary chargers Reset by moving Operating Mode are rapidly flashing se...