background image

pag. 20

9

EXTERNAL PROBE

9.1 INSTALLING AND CONNECTING  

EXTERNAL PROBE

9.2 SETTING HEATING CURVE

9.3 ADJUSTING HEATING CURVE SET

When the external probe is used, the electronic board
calculates the boiler delivery temperature according to
the outside temperature.
The ratio of these temperatures is summarised in the
diagram in figure 9.2-1.

T

HIS MUST BE FITTED OTHERWISE BOILER WILL NOT PERFORM

AT THE MAXIMUM EFFICENCY

.

The most suitable curve should be chosen according
to the design temperature and the type of building.
To set a new curve (see “parameters that can be set”
in paragraph above):

-  access parameter P5
-  set the preselected value
-  store to set value in memory

To mount the external probe:

-

remove protective cover as
shown here

-

insert probe cable through
hole intended to be used. We
recommend mounting a rubber
cable duct if the rear route is
used (see ref. 1), a suitable
cable holder if the lower one is
used (see ref. 2); cable duct
and cable holder are not sup-
plied.

.

If solution 2 is used, remove
the lower section  the protecti-
ve cover.

-

connect the wires to the probe
and the boiler following the
wiring diagram on page 14.

20

-20

-15

-10

-5

0

5

10

15

20

30

40

50

60

70

80

90

2

n

4

6

8

10

12

14

16

18

20

Temperatura esterna mediata (

°

C)

Valore della pendenza della curva di riscaldamento

Curve di riscaldamento

Valore della pendenza della curva di riscaldamento
impostato in fabbrica= 15

24

22

28

32

36

40

25

1

2

3

H

1/2 H

min. 2,5 m

In order to adjust the heating curve, parameter P6 is
used. In this mode, the heating curve is shifted in
parallel so as to change the delivery temperature cal-
culated (see example in fig. 9.2-2).

To set the shift, proceed as follows (see “parameters
that can be set” in paragraph above):

-  access parameter P6
-  set preselected value
-  store set value in memory

fig. 9.1-1

fig. 9.1-2

fig. 9.1-3

fig. 9.2-1

DO NOT INSTALL EXTER-
NAL PROBE IN POSI-
TIONS INDICATED
BELOW: 

CORRECT INSTALLATION POSITION:

PROBE SHOULD BE INSTALLED ON
A NORTH ORNORTH EAST FACING
WALL AND SHELTERED FROM THE
EFFECT OF THE SUN’S RAYS AND
FROM OTHER HEAT SOURCES

value of slope of heating curve

heating curve

Factory-set value of slope of heating curve = 15

Mean outside temperature (°C)

Calculated flow temperature (

°C)

Summary of Contents for OPTIMA 28 CB

Page 1: ...OPTIMA 28 CB AND 28 SB WALL MOUNTED GAS BOILERS INSTALLATION INSTRUCTIONS...

Page 2: ...25 15 Examples of installation pag 26 16 Accessories pag 27 17 Periodic appliance maintenance and cleaning pag 28 18 Short parts list pag 31 19 Balanced flue kits pag 33 1 Warnings pag 3 1 1 Use of an...

Page 3: ...e without the express written permission of Trianco Ltd could invalidate the appliance warranty and infringe the Gas Safety Installation and Use Regulations Incorrect installation may cause harm to pe...

Page 4: ...engineer to ensure the system is in good working order 1 3 SAFETY ADVICE In floor systems the use of plastic pipes without protection against penetration of oxygen through the walls can cause corrosio...

Page 5: ...comfort in all conditions DOMESTIC HOT WATER DRAW OFF CB MOD When calling for domestic hot water the boiler by means of an appropriate sensor automatically switches over in order to guarantee supply o...

Page 6: ...5 Class of NOx emissions EN 483 Cl 5 5 5 5 Combustion efficiency 97 9 97 9 97 9 97 9 Flue Gas mass range at nominal capacity kg h 43 5 43 5 43 5 43 5 Residual flue gas discharge head Pa 73 73 73 73 Ga...

Page 7: ...m Filling Valve 14 Domestic water pressure switch 15 Domestic water temperature sensor 16 Bypass 17 Delivery temperature sensor 18 Three way valve 19 Condensation Trap A Heating Flow B Domestic hot wa...

Page 8: ...3 bar The pressure relief discharge pipe should be not less than 15mm dia run continuously downward and preferably over a drain It should be routed in such a manner that no hazard occurs to occupants...

Page 9: ...ick opening window etc 300 Vertical Flues minimum distance to edge of terminal mm P Above the roof level to base of terminal 300 Q From adjacent wall to flue 300 R From adjacent opening window 1000 S...

Page 10: ...t rawlplugs and mounting bolts 2 Fix the boiler to the wall using the wall mounting bracket 3 Pass the terminal through the wall and fit the internal wall seal to the terminal 4 Fit the 60mm black sea...

Page 11: ...SUPPLIED EXTRA PIPES CAN BE PURCHASED TO EXTEND TO 4 MTRS L H SIDE OUTLET HORIZONTAL BALANCED FLUE HIGH LEVEL HORIZONTAL BALANCED FLUE MAX MIN WALL THICKNESS IS WITH KIT SUPPLIED EXTRA PIPES CAN BE P...

Page 12: ...all sections are pushed firmly home Secure bot tom section to boiler with clamp 7 Fit a roof flashing sleeve to the roof not supplied and insert Vertical Flue Terminal through flashing from the outsi...

Page 13: ...pag 13 A B C D A B 2500mm MAX C D 4000mm MAX NOTE For each additional elbow reduce straight lengths by the relevant elbow dimension 90 1500mm and 45 750mm 90 BEND 1000mm 45 BEND 750mm...

Page 14: ...ower them both together fig 5 3 5 ACCESS TO ELECTRICAL PANEL FOR CON NECTING ADDITIONAL UNITS CONTROL PANEL BOILER CONTROL PANEL COVER fig 5 2 fig 5 3 V2 V1 fig 5 1 In order to connect any external co...

Page 15: ...0 VAC Configurable connection 230 VAC Ionisation probe Gas valve mains gas 230 VAC Ignition electrode Ignition transformer 230 VAC AC 24V Transformer Fan motor 2 3 1 2 3 1 4 2 3 1 4 5 2 3 1 4 5 6 2 3...

Page 16: ...INARY CHECKS TO BE CARRIED OUT BEFORE APPLIANCE START UP The water pressure is checked periodically on the pressure gauge described in paragraph 7 1 In order to reset the pressure to within the preset...

Page 17: ...de with knobs B and C Heating and domestic hot water temperatures remain unchanged even after power supply fai lure MODE BUTTON The MODE button makes it possi ble to switch from summer to winter opera...

Page 18: ...is play returns to reading 1 in all cases after some minutes the boiler temperature display is reset RESET BUTTON RESETTING THE APPLIANCE After an operating irregularity the boiler stops for safety re...

Page 19: ...b3 not used b4 letter of outside temperature C b5 not used b6 not used b7 second zone circuit temperature C C1 letter of ionisation current value A C2 letter of number of fan revolutions thousands an...

Page 20: ...the lower section the protecti ve cover connect the wires to the probe and the boiler following the wiring diagram on page 14 20 20 15 10 5 0 5 10 15 20 30 40 50 60 70 80 90 2 n 4 6 8 10 12 14 16 18...

Page 21: ...icult to use the heating system eg in summer or with a floor radiant panel system it is possible to use the domestic hot water circuit by proceeding as follows rotate the control panel forward para 5...

Page 22: ...what is described below If the values found are different proceed as follows Turn gas valve capacity regulator 2 figure 10 3 clockwise to increase anticlockwise to decrease value of CO2 reading given...

Page 23: ...ermostat or deactivate the hea ting by pressing the MODE button LED F goes out This will ensure that the antiseize function and other functions designed for the appliance safety and com fort still ope...

Page 24: ...URE CODE DISPLAY A fault or temporary failure is indicated by a three figure code appearing on the display Two of them can be presen ted on the display and then the code is indicated showing alternati...

Page 25: ...sconnected not used 82 Incompatible LPB address not used 91 Fault inside board 92 Fault inside board 100 Incorrect configuration of clocks in connection with RVA not used 110 Fault due to overtemperat...

Page 26: ...M CR TA SI OPTIMA SB MOD SE External probe CR TA QAA73 programmer room thermostat YD 3 way valve for hot water production TB Domestic hot water tank temperature probe SI high temp safety therostat fo...

Page 27: ...remote control according to weekly and hourly setting with yearly date setting which has functions of monitoring boi ler and programming zone sensor alarm indicators and advanced diagnostics fig 16 1...

Page 28: ...er is cool Ensure that both the gas and electrical supplies to the boiler are isolated Caution All gaskets removed must be checked and possibly replaced if they are damaged or worn To access inside of...

Page 29: ...17 8 Remove pneumatic and electrical fan connections and disconnect gas pipe Remove nuts E1 unthread MIXER E FAN F unit fig 17 6 Extract internal choke G and inspect O ring with the aid of a brush or...

Page 30: ...flue H from boiler shell fig 17 6 and with the aid of a brush and vacuum cleaner clean between the exchange rungs fig 17 9 When the parts are replaced take care to reinsert them in the correct order p...

Page 31: ...ON ELECTRODE BFE01064 23 CENTRIFUGE FAN W150 4 32 IMMERSION SENSOR S300 1 36 CIRCULATOR P158 37 AUTOMATIC ESCAPE VALVE G207 1 39 WATER GAUGE G603 3 40 GAS VALVE UNIT GRVAL001 41 CIRCULATOR CONSENSUS D...

Page 32: ...1001 19 IGNITION ELECTRODE BFE01019 20 ELECTRODE GASKET CFG01009 21 DETECTION ELECTRODE BFE01064 23 CENTRIFUGE FAN W150 4 32 SENSOR S300 1 35 CIRCULATOR P158 35 1 AUTOMATIC ESCAPE VALVE G207 1 36 MINI...

Page 33: ...1 3 510028 100mm seal 1 Item Part No Description Qty 1 510023 90 concentric bend 1 2 510027 60mm seal Blue 1 3 510028 100mm seal 1 Item Part No Description Qty 1 510024 45 concentric bend 1 2 510027 6...

Page 34: ......

Page 35: ......

Page 36: ...service division is notified promptly of any defects Under the terms of guarantee the appliance must be made available for service during normal working hours Monday to Friday weekend work not accep...

Reviews: