background image

Forte

Table B

Note: 

Cable selection is dependent on 

derating factors

Twin and earth PVC insulated cable

Current carrying capacity

In conduit

trunking

6 mm²

38A

10 mm²

52A

16 mm²

69A

Installed in an 

insulated wall

6 mm²

32A

10 mm²

43A

16 mm²

57A

Clipped direct

or buried in a 

non-insulated 

wall

6 mm²

46A

10 mm²

63A

16 mm²

85A

The installation, supply cable and circuit 
protection must conform with BS 7671 (IEE 
wiring regulations) and be sufficient for the 
amperage required.
The following notes are for guidance only:

1

1.1

2

3

3.1

4

4.1

4.2

5

5.1

6

6.1

7

7.1

7.2

8

9

9.1

9.2

10

10.1

10.2

10.3

E-002-A

The shower must only be connected to a 
230-240V ac supply. If you are installing a 
shower with a kilowatt rating above 9kW, 
it is advisable to contact the local 
electricity supply company.
The electrical rating of the shower is 
shown on the rating label 

(Fig.  )

 within 

the unit.
Before making any sort of electrical 
connection within the installation make 
sure that no terminal is live. If in any 
doubt, switch off the whole installation at 
the mains supply and remove the correct 
fuse.
The shower must be connected to its own 
independent electrical circuit. IT MUST 
NOT be connected to a ring main, spur, 
socket outlet, lighting circuit or cooker 
circuit.
The electrical supply must be adequate for 
the loading of the unit and existing 
circuits.
Check your consumer unit (main fuse box) 
has a main switch rating of 80A or above 
and that it has a spare fuse way which will 
take the fuse or Miniature Circuit Breaker 
(MCB) necessary for the shower 

(Fig.  )

.

If your consumer unit has a rating below 
80A or if there is no spare fuse way, then 
the installation will not be straightforward 
and may require a new consumer unit 
serving the house or just the shower.
You will need to contact the local 
electricity company. They will check the 
supply and carry out what is necessary. 
They will also check the main bonding.
The earth continuity conductor of the 
electrical installation must be effectively 
connected electrically to all exposed metal 
parts of other appliances and services in 
the room in which the shower is to be 
installed, to conform to current IEE 
regulations.
All exposed metallic parts in the bathroom 
must be bonded together using a cable of 
at least 4 mm² cross sectional area. These 
parts include metal baths, radiators, water 
pipes, taps and waste fittings.
For close circuit protection DO NOT use a 
rewireable fuse. Instead use a suitably 
rated Miniature Circuit Breaker (MCB) or 
cartridge fuse 

(see Table A)

.

In the interest of electrical safety a 30mA 
residual current device (RCD) should be 
installed in all UK electric and pumped 
shower circuits. This may be part of the 
consumer unit or a separate unit.
A 45 amp double pole isolating switch 
with a minimum contact gap of 3 mm in 
both poles must be incorporated in the 
circuit.
It must have a mechanical indicator 
showing when the switch is in the OFF 
position, and the wiring must be 
connected to the switch without the use of 
a plug or socket outlet.
The switch must be accessible and clearly 
identifiable, but out of reach of a person 
using a fixed bath or shower, except for 
the cord of a cord operated switch, and 
should be placed so that it is not possible 
to touch the switch body while standing in 
a bath or shower cubicle. It should be 
readily accessible to switch off after using 
the shower.
Where shower cubicles are located in any 
rooms other than bathrooms, all socket 
outlets in those rooms must be protected 
by a 30mA RCD.
The current carrying capacity of the cable 
must be at least that of the shower circuit 
protection 

(see Table B)

.

To obtain full advantage of the power 
provided by the shower, use the shortest 
cable route possible from the consumer 
unit to the shower.
It is also necessary to satisfy the 
disconnection time and thermal 
constraints which means that for any given 
combination of current demand, voltage 
drop and cable size, there is a maximum 
permissible circuit length.
The shower circuit should be separated 
from other circuits by at least twice the 
diameter of the cable or conduit.
The current rating will be reduced if the 
cabling is bunched with others, 
surrounded by thermal loft or wall 
insulation or placed in areas where the 
ambient temperature is above 30°C. Under 
these conditions, derating factors apply 
and it is necessary to select a larger cable 
size.

In the majority of installations, the cable 
will unavoidably be placed in one or 
more of the above conditions. This 
being so, it is strongly recommended to 
use a minimum of 10 mm cabling 
throughout the shower installation.

In any event, it is essential that individual 
site conditions are assessed by a 
competent electrician in order to 
determine the correct cable size and 
permissible circuit length.

ELECTRICAL REQUIREMENTS

The installation, supply cable and circuit 
protection must conform with BS 7671 (IEE 
wiring regulations) and be sufficient for the 
amperage required.
The following notes are for guidance only:

1

1.1

2

3

3.1

4

4.1

4.2

5

5.1

6

6.1

7

7.1

7.2

8

9

9.1

9.2

10

10.1

10.2

10.3

E-002-A

The shower must only be connected to a 
230-240V ac supply. If you are installing a 
shower with a kilowatt rating above 9kW, 
it is advisable to contact the local 
electricity supply company.
The electrical rating of the shower is 
shown on the rating label 

(Fig.  )

 within 

the unit.
Before making any sort of electrical 
connection within the installation make 
sure that no terminal is live. If in any 
doubt, switch off the whole installation at 
the mains supply and remove the correct 
fuse.
The shower must be connected to its own 
independent electrical circuit. IT MUST 
NOT be connected to a ring main, spur, 
socket outlet, lighting circuit or cooker 
circuit.
The electrical supply must be adequate for 
the loading of the unit and existing 
circuits.
Check your consumer unit (main fuse box) 
has a main switch rating of 80A or above 
and that it has a spare fuse way which will 
take the fuse or Miniature Circuit Breaker 
(MCB) necessary for the shower 

(Fig.  )

.

If your consumer unit has a rating below 
80A or if there is no spare fuse way, then 
the installation will not be straightforward 
and may require a new consumer unit 
serving the house or just the shower.
You will need to contact the local 
electricity company. They will check the 
supply and carry out what is necessary. 
They will also check the main bonding.
The earth continuity conductor of the 
electrical installation must be effectively 
connected electrically to all exposed metal 
parts of other appliances and services in 
the room in which the shower is to be 
installed, to conform to current IEE 
regulations.
All exposed metallic parts in the bathroom 
must be bonded together using a cable of 
at least 4 mm² cross sectional area. These 
parts include metal baths, radiators, water 
pipes, taps and waste fittings.
For close circuit protection DO NOT use a 
rewireable fuse. Instead use a suitably 
rated Miniature Circuit Breaker (MCB) or 
cartridge fuse 

(see Table A)

.

In the interest of electrical safety a 30mA 
residual current device (RCD) should be 
installed in all UK electric and pumped 
shower circuits. This may be part of the 
consumer unit or a separate unit.
A 45 amp double pole isolating switch 
with a minimum contact gap of 3 mm in 
both poles must be incorporated in the 
circuit.
It must have a mechanical indicator 
showing when the switch is in the OFF 
position, and the wiring must be 
connected to the switch without the use of 
a plug or socket outlet.
The switch must be accessible and clearly 
identifiable, but out of reach of a person 
using a fixed bath or shower, except for 
the cord of a cord operated switch, and 
should be placed so that it is not possible 
to touch the switch body while standing in 
a bath or shower cubicle. It should be 
readily accessible to switch off after using 
the shower.
Where shower cubicles are located in any 
rooms other than bathrooms, all socket 
outlets in those rooms must be protected 
by a 30mA RCD.
The current carrying capacity of the cable 
must be at least that of the shower circuit 
protection 

(see Table B)

.

To obtain full advantage of the power 
provided by the shower, use the shortest 
cable route possible from the consumer 
unit to the shower.
It is also necessary to satisfy the 
disconnection time and thermal 
constraints which means that for any given 
combination of current demand, voltage 
drop and cable size, there is a maximum 
permissible circuit length.
The shower circuit should be separated 
from other circuits by at least twice the 
diameter of the cable or conduit.
The current rating will be reduced if the 
cabling is bunched with others, 
surrounded by thermal loft or wall 
insulation or placed in areas where the 
ambient temperature is above 30°C. Under 
these conditions, derating factors apply 
and it is necessary to select a larger cable 
size.

In the majority of installations, the cable 
will unavoidably be placed in one or 
more of the above conditions. This 
being so, it is strongly recommended to 
use a minimum of 10 mm cabling 
throughout the shower installation.

In any event, it is essential that individual 
site conditions are assessed by a 
competent electrician in order to 
determine the correct cable size and 
permissible circuit length.

ELECTRICAL REQUIREMENTS

Summary of Contents for Forte

Page 1: ...Installers please note these instructions are to be left with the user 2180686A February 2008 Installation and operating instructions Forte electric shower ...

Page 2: ... the cover 12 Commissioning 13 Operating the shower 14 Operating functions 16 Cleaning 17 Instructions for installers and service engineers only 18 Spare parts 19 Fault finding 20 Guarantee service policy etc rear cover CONTENTS Page To check the product suitability for commercial and multiple installations please contact Triton s specification advisory service before installation Telephone 0870 0...

Page 3: ...er temperatures and could also cause the Pressure Relief Device in the unit to operate This product is not suitable for mounting into steam rooms or steam cubicles PLUMBING The plumbing installation must comply with Water Regulations Building Regulations or any particular regulations as specified by Local Water Company or Water Undertakers and should be in accordance with BS 6700 The supply pipe m...

Page 4: ...g It is the flow rate of the water passing through the heater unit which determines the shower temperature at any given setting the slower the flow the hotter the water becomes and the faster the flow the cooler the water b During winter mains water supply will be cooler than in summer Therefore the temperature of the shower will vary between seasons on any one setting of the temperature control e...

Page 5: ...switch assembly 9 Stabilising valve 10 Terminal block 11 Earth connection 12 Solenoid valve 13 Water inlet 14 Outlet temperature limiter 15 Pressure relief device PRD 16 Trimplate 17 Shower outlet Pack contents Shower unit Screw fixing kit Instructions guarantee etc 255 mm 305 mm 210 mm 59 mm Fig 1 NOTE Not all wiring has been shown for reasons of clarity 1 2 3 4 6 7 8 9 10 11 12 13 14 15 16 3 17 ...

Page 6: ... area These parts include metal baths radiators water pipes taps and waste fittings For close circuit protection DO NOT use a rewireable fuse Instead use a suitably rated Miniature Circuit Breaker MCB or cartridge fuse see Table A In the interest of electrical safety a 30mA residual current device RCD should be installed in all UK electric and pumped shower circuits This may be part of the consume...

Page 7: ...that of the shower circuit protection see Table B To obtain full advantage of the power provided by the shower use the shortest cable route possible from the consumer unit to the shower It is also necessary to satisfy the disconnection time and thermal constraints which means that for any given combination of current demand voltage drop and cable size there is a maximum permissible circuit length ...

Page 8: ...10 bar Note If the stated flow rate is not available it may not be possible to achieve the best performance from the unit throughout the year For guidance on the running and static pressures contact the local Water Authority or consult a competent plumber During periods of high ambient temperatures it may be necessary to select a low power setting to achieve your preferred shower temperature The w...

Page 9: ...Do not operate the shower with a damaged or kinked shower hose or a blocked showerhead which can cause the PRD to operate When commissioning the showerhead must be removed from the flexible hose while at the same time the temperature control must be at the minimum flow position Failure to follow this procedure may also cause the PRD to operate Make sure the shower is positioned over a bath or show...

Page 10: ...rarily place the trimplate into position then mark the pipe entry on the side of the trimplate Carefully remove the appropriate area using a junior hacksaw If installing a feed pipe from the back or bottom the centre of the inlet valve to the wall surface is 20 mm fig 9 Note If entry is from the back the nut of the compression fitting will be partially behind the surface of the wall This area must...

Page 11: ...position leaving the base of the screw head protruding 6 mm out from the wall Hook the backplate over the top screw and fit the bottom fixing screw into position Do not fully tighten the screws at this stage as the fixing holes are elongated to allow for out of square adjustment after the plumbing connections have been completed Fig 10 20 mm Fig 9 ...

Page 12: ... and turning on the mains water supply long enough to clear the debris to waste Procedure Turn off the water supply either at the mains stopvalve or the isolating stopvalve Connect the mains water supply to the inlet of the shower via 15 mm copper stainless steel or plastic pipe using a 15 mm x 15 mm brass compression fitting Note The inlet fitting is designed to enter a compression fitting only D...

Page 13: ...to terminal marked L Important Fully tighten the terminal block screws and make sure that no cable insulation is trapped under the screws Loose connections can result in cable overheating Note The supply cable earth conductor must be sleeved The outer sheath of the supply cable must be stripped back to the minimum The supply cable must be secured either by routing through conduit or in trunking or...

Page 14: ...e the temperature control fully anti clockwise Remove the cover and position the temperature control knob so that it points to the maximum flow position fig 14 Position the power selector to the stop position fig 15 Replace the cover squarely to the backplate and guide into position so that the knobs locate correctly into the splined spindles Should any difficulty arise recheck the points above Se...

Page 15: ... The power indicator will light Switch the power selector to the COLD position fig 17 and wait until water starts to flow from the flexible hose Slowly rotate the temperature control fully anti clockwise to the maximum flow position fig 18 It will take about thirty seconds for a smooth flow of water to be obtained while air and any debris is being dispersed from the shower When a smooth flow of wa...

Page 16: ... the water temperature The red symbol is the economy setting for using less power during warmer months Temperature adjustment at this setting is via the temperature control Note If the stated flow rate required for the unit cannot be met due to low water pressure it will be necessary to operate the unit on economy setting during the warmer months because of flow rate limitations entering the unit ...

Page 17: ...kwise fig 20 this will increase the flow of water through the shower To increase the shower temperature Turn the temperature control clockwise fig 21 this will decrease the flow of water through the shower Note It is advisable to be certain that the showering temperature is satisfactory by testing with your hand before stepping under the showerhead There will always be a time delay of a few second...

Page 18: ...n overheat temperature is sensed power to the elements will be reduced Water will continue to flow When the temperature has cooled sufficiently power to the elements will be automatically restored to the previous setting at the time of interruption Safety cut out The unit is fitted with a non resettable thermal cut out safety device In the event of abnormal operation which could cause unsafe tempe...

Page 19: ... It is important to keep the showerhead clean to maintain the performance of the shower The hardness of the water will determine the frequency of cleaning For example if the shower is used every day in a very hard water area it may be necessary to clean the showerhead on a weekly basis WARNING Do not use abrasive or aggressive cleaning products when cleaning the shower as they may damage the unit ...

Page 20: ...ect and remove the compression fitting Also depending on the incoming pipework arrangements and if there is not enough slack in the pipework it may be necessary to remove the unit from the wall When cleaning the filter do not use a sharp object as it will cause damage It is preferable to use an old toothbrush or similar When the filter is clean recommission the unit Filter Fig 23 Instructions for ...

Page 21: ...nd wire assembly 82300970 4 Can assembly 8 5kW P07810700 5 Stabiliser valve assembly 82600550 6 Solenoid valve assembly 83300450 7 Outlet pipe assembly incl terminal block wires S09201101 8 Pressure Relief Device PRD 82800450 9 Trimplate 7052921 10 Front cover assembly P15930602 11 Pipe trim backplate trimplate 7052920 Spare parts SPARE PARTS 10 11 1 2 3 4 5 6 7 8 9 ...

Page 22: ...pliances and if necessary contact local the Electricity Supply Company 1 2 1 Have unit checked Ring Customer Service 2 1 1 Increase flow rate via temperature control 2 1 2 Blocked showerhead clean or replace blocked sprayplate in showerhead 2 2 1 Check if stop valves are fully open Check if there is a blockage in the inlet filter 2 3 1 Readjust flow rate to give increased flow 2 3 2 Select economy...

Page 23: ...service engineer or contact Customer Service 5 1 1 Wait until the water pressure returns to normal 6 1 1 Clean or replace blocked sprayplate in showerhead and then fit new PRD 6 2 1 Check for free passage through hose Replace the hose if necessary and fit new PRD 6 3 1 Fit new PRD Commission unit with showerhead removed Note Identify cause of operation before fitting new PRD unit When fitting a ne...

Page 24: ... uk Triton Showers Triton Road Nuneaton Warwickshire CV11 4NR Triton is a division of Norcros Group Holdings Limited Triton Standard Guarantee Triton guarantee this product against all mechanical and electrical defects arising from faulty workmanship or materials for a period of two years for domestic use only from the date of purchase provided that it has been installed by a competent person in f...

Page 25: ...Pdf Supplied By http www plumbworld co uk ...

Reviews: