FLAMMABLE GAS SENSOR/TRANSMITTER
A T E X
M1
GROUP I & II
INTRINSICALLY
SAFE
6 CONNECTIONS
continued
Group II sensor connections using zener safety barriers.
Max. Cable Length: 1 km using 1.5 mm
2
cable conductors.
If you require any help with the use and connection of hazardous area equipment
please contact the Trolex Technical Department.
Power Safety Barrier:
Signal Safety Barrier:
1 2 3 4 5
Supply
6 7 8
1
2
4
3
MTL 787S+
MTL 779+
+24 V
0 V
0 V
0 V
+V
1
2
4
3
4 to 20 mA
Signal
HAZARDOUS
SAFE
TX6383.02
Group II sensor connections using isolation safety barriers.
Max. Cable Length: 1 km using 1.5 mm
2
cable conductors.
Power Isolation Barrier:
Pepperl & Fuchs
KFD2–SL2–EX 2B
Signal Isolation Barrier:
Pepperl & Fuchs
KFD2–STC4-EX 1
1 2 3 4 5
Supply
6 7 8
1
2
8
7
3
11
12
KFD2–STC4-EX 1
KFD2–SL2–EX 2B
+24 V
0 V
0 V
0 V
+V
8
9
7
4
5
1
2
15
14
4 to 20 mA
Signal
HAZARDOUS
SAFE
TX6383.02
13/28
INSTALLATION & OPERATING DATA
TT X
X 66 33 88 33
ISSUE S 01/15