SYSTEM # 2 - Engine speed/RPM control and many other applications

On applications other than 

“On-To-Run” fuel shut down, a solenoid electronic control module is required  to allow the solenoid to operate in 

a continuous duty mode without damaging the solenoid.  W ire the solenoid and module as shown below.   Do Not mount the module 
directly on the engine or other high vibration point.  Keep module away from direct heat sources.

WIRED DIRECT (S500-A5)

WIRED FOR REMOTE OPERATION (S500-A6)

3. S500-A5 & A50 Modules - After making the final wiring check, energize the solenoid hold coil by turning the switch to the 

“on” position and 

manually push the solenoid plunger to the seated position.  The plunger should remain  seated.  
S500-A6 & A60 Modules - After making the final wiring check, energize the solenoid hold coil by turning the switch to the 

“on” position, close 

the run switch on the module and manually push the solenoid plunger to the seated position.  The plunger should remain  seated. 

4

.  

W ith solenoid seated, connect the linkage to the plunger , adjust the linkage for proper operation and tighten  all connection points securely. 

5.   De-energize the solenoid.  Visually check the linkage by manually moving the linkage thought its entire stroke to make sure the linkage is 

free from obstructions.  Total movement of the plunger

MUST NOT 

exceed the recommended stroke of the solenoid.

X190 (H10558) Revision 8/23/07 Trombetta Corporation

WIRED DIRECT (S500-A50)

WIRED FOR REMOTE OPERATION (S500-A60)

24 Volt 
Installations

Although the 
module is capable 
of 12 or 24 volt 
input, only the 12 
volt system can be 
wired with its 
output going 
directly to the 
solenoid as 
depicted in the 
diagrams above.  
The 24 volt output 
(pull-in) MUST be 
wired through an 
external contactor.  
Failure to do so will 
result in reduced 
module life.

*** Note when using an S500-A50 or 
S500-A60 module all of the solenoid 
connections must connect to the 
module as shown. 

Do not

connect any 

of the solenoid leads to another ground 
point in the system.

* Note - some solenoids only have 2 wires.  
If this is the case, use the black and either 
the white or red wire connection points on 
the module

WIRED DIRECT (S500-A5)

WIRED FOR REMOTE OPERATION (S500-A6)