background image

EN

15

desiccant dehumidifier TTR 160 / TTR 250

Spare parts drawing and list TTR 160

Info

The position numbers of the spare parts differ from
those describing the positions of the components
mentioned in these instructions.

Item

Designation

Article number

Item

Designation

Article number

1

Basic housing

P 1000 3927

15

Filter mat

P 1000 1192

2

Cover

P 1000 3925

16

Gear motor

P 1000 1038

3

Rotor cassette

P 1000 3924

17

Toothed belt pulley

P 1000 1064

4

Rubber tensioner

P 1000 1059

18

Pressure spring

P 1000 1055

5

Heating frame

P 1000 3920

19

Pressure spring

P 1000 1056

6

Handle

P 1000 1246

20

Heating plate

P 1000 1102

7

Fan

P 1000 1073

21

Heating element

P 1000 1182

8

Relay

P 1000 0195

22

Toothed belt

P 1000 1063

9

Switch

P 1000 1077

23

Rotor

P 1000 1035

10

Connection socket

P 1000 1049

24

Needle bush

P 1000 1061

11

Protective cap

P 1000 1053

25

Foot

P 1000 1060

12

Ammeter

P 1000 1058

26

Mounting clip for relay

P 1000 0196

13

Operating hours counter

P 1000 1137

27

Lock nut for cable bushing

P 1000 1205

14

Cable bushing

P 1000 0973

28

Exhaust air hose

P 1000 1669

Summary of Contents for 1110000120

Page 1: ...TRT BA TTR160 TTR250 TC2021 14 004 EN TTR 160 TTR 250 EN ORIGINAL INSTRUCTIONS DESICCANT DEHUMIDIFIER ...

Page 2: ...mation marked with this symbol helps you to carry out your tasks quickly and safely Follow the manual Information marked with this symbol indicates that the instructions must be observed You can download the current version of the instructions and the EU declaration of conformity via the following link TTR 160 https hub trotec com id 45044 TTR 250 https hub trotec com id 45045 Safety Read this man...

Page 3: ...he nameplate Additionally information regarding the electrical connection is provided in the technical annex Insert the mains plug if any into a properly secured mains power socket Observe the device s power input cable length and intended use when selecting extensions to the power cable Completely unroll extension cables Avoid electrical overload If you do not use the device for extended periods ...

Page 4: ...erheating and fire hazards the device must not be covered Personnel qualifications People who use this device must be aware of the dangers that occur when working with electric devices in damp areas have read and understood the instructions especially the Safety chapter Instructed person Instructed persons have been informed of the tasks they were entrusted with as well as of potential hazards res...

Page 5: ... and storage facilities where a particularly low humidity level is required over a broad temperature range The desiccation technique enables the safe and economic operation even at low operating temperatures The desiccant dehumidifier works with a desiccant wheel rotor which is composed of layers of smooth and corrugated non woven fabric with chemically bonded silica gel Thus created is a honeycom...

Page 6: ...points Subsequently the air current is led through a heater battery 7 and heated to approx 100 to 120 C depending on the intake temperature Simultaneously the relative humidity is extremely reduced In passing through the regeneration sector 2 the thus prepared air now again absorbs the moisture retained by the silica gel desorption Then the extremely humid regeneration air 8 is discharged to the o...

Page 7: ...ediate neutralization with the moist exhaust air the humid air outlet should be guided away with a minimum distance of approx 1 m in case of direct intake devices Scope of delivery The scope of delivery of the device contains 1 x Dehumidifier 1 x Connection cable 1 x Instructions There are further accessories optionally available which can be obtained from the Trotec customer service Default setti...

Page 8: ...s case the fan can be configured for permanent operation by replugging a plug contact at the integrated relay This operation may only be carried out by an electrically skilled person If required please contact the Trotec customer service Errors and faults Error Diagnosis Potential cause Remedy No dehumidi fication Dry air shows no temperature increase Rotor drive defective Check rotor drive and ha...

Page 9: ...rained personnel or by the Trotec customer service The device is designed for long hours of operation with minimum maintenance effort Safe operation of the device requires all built in components to be checked and cleaned after 6 months at the latest or after every 4 000 operating hours as well as all damaged components to be replaced Filter change Warning Risk of injury due to fan Make sure to sw...

Page 10: ...device Note Device may be damaged by liquid Before reinserting the air filter make sure it has dried completely Otherwise there is a risk of the fan sucking in liquid leading to a short circuit and consequential damage 4 Reinsert the air filter into the device 5 Put the cover back onto the device and tighten the screw ...

Page 11: ...uctivity of the silica gel1 8 ammonia NH3 destruction of the silica gel structure 9 hydrofluoric acid HF destruction of the mechanical strength of the rotor material 10 aluminium chloride AlCl3 reduced productivity of the silica gel1 11 sea water reduced productivity of the silica gel1 12 steam with a high temperature destruction of the silica gel structure 13 softener clogging of the silica gel s...

Page 12: ...nal humid air flow rate static pressure 35 m3 h 25 Pa 50 m3 h 100 Pa Intake temperature 15 C to 35 C 15 C to 35 C Ambient temperature 20 C to 40 C 20 C to 40 C Mains connection 230 V 50 60 Hz 230 V 50 60 Hz Total power consumption 0 65 kW 1 3 kW Power consumption heating 0 6 kW 1 2 kW Heating current min opt max 2 0 2 3 2 6 A 4 5 5 0 5 5 A Length approx 375 mm 410 mm Width approx 300 mm 150 mm Hei...

Page 13: ...EN 13 desiccant dehumidifier TTR 160 TTR 250 Circuit diagram TTR 160 Circuit diagram TTR 250 ...

Page 14: ...14 EN desiccant dehumidifier TTR 160 TTR 250 Dimensions TTR 160 Dimensions TTR 250 ...

Page 15: ... P 1000 1064 4 Rubber tensioner P 1000 1059 18 Pressure spring P 1000 1055 5 Heating frame P 1000 3920 19 Pressure spring P 1000 1056 6 Handle P 1000 1246 20 Heating plate P 1000 1102 7 Fan P 1000 1073 21 Heating element P 1000 1182 8 Relay P 1000 0195 22 Toothed belt P 1000 1063 9 Switch P 1000 1077 23 Rotor P 1000 1035 10 Connection socket P 1000 1049 24 Needle bush P 1000 1061 11 Protective cap...

Page 16: ... P 1000 1066 4 Rubber tensioner P 1000 1059 18 Pressure spring P 1000 1055 5 Heating frame P 1000 3932 19 Pressure spring P 1000 1056 6 Handle P 1000 1246 20 Heating plate P 1000 1103 7 Fan P 1000 1074 21 Heating element P 1000 1075 8 Relay P 1000 0195 22 Toothed belt P 1000 1065 9 Switch P 1000 1077 23 Rotor P 1000 1036 10 Connection socket P 1000 1049 24 Needle bush P 1000 1061 11 Protective cap...

Page 17: ...quipment Declaration of conformity Declaration of conformity in accordance with the EC Machinery Directive 2006 42 EC Annex II Part 1 Section A We Trotec GmbH declare in sole responsibility that the product designated below was developed constructed and produced in compliance with the requirements of the EC Machinery Directive in the version 2006 42 EC Product model Product TTR Product type desicc...

Page 18: ...Trotec GmbH Grebbener Str 7 D 52525 Heinsberg 49 2452 962 400 49 2452 962 200 info trotec com www trotec com ...

Reviews: