Maintenance report checklist
Maintenance work
Ventilation ATEX
Smoke exhaust fan
to be carried out in the relevant
category
As
standard
with VD
with VD
+VME
with moni-
toring
system
To be carried out every six months by instructed personnel
Fan is free of foreign matter (tools,
dirt, etc.).
☐
☐
☐
☐
To be performed annually by instructed personnel
Visual check of the general external
condition of the device, contamina-
tion, damage and corrosion, and
clean if necessary
☐
☐
☐
☐
☐
☐
Check flexible connector(s) for
damage and ensure stress-free
installation
☐
☐
☐
☐
☐
☐
Check the cooling air supply for a
free cross section (VD monitors the
motor temperature) - if present
☐
☐
☐
☐
Check the anti-vibration elements
for free movement and damage
☐
☐
☐
Check the electrical fan terminal
box and cables for damage and
correct installation
☐
☐
☐
☐
☐
☐
Check the impeller for damage and
free movement
☐
☐
☐
Perform a functional check: 20
minutes
2
☐
☐
☐
☐
☐
☐
Check the direction of rotation
☐
☐
☐
☐
☐
☐
Check the electric motor’s current
consumption
☐
☐
☐
☐
Measurement and evaluation of the
bearing condition
☐
Read off the VD display (check
“traffic lights” and display values) or
read out data
☐
☐
To be performed annually by specialist personnel
Check the vibration state
3
☐
☐
☐
2
Note: In the construction with VD, the first functional check is automatically saved as the reference run. This is used as a comparison for all
subsequent functional checks under the same operating conditions
3
The values specified in the operating manual must be observed. The values must be determined according to ISO 14694.
4
The service life of the bearings is generally 20,000 h, but the actual service life can deviate considerably from this value depending on the
bearing load. The operating instructions provided by the motor manufacturer are available for download from the manufacturer’s website.
5
Recommendation: An annual bearing check should be performed.
Maintenance report
Centrifugal fans REH; RZH; BVREH; BVRA
50