background image

Inspection, maintenance and repair measures

Interval Maintenance work

Personnel

A

Accessibility of the smoke control damper

Internal and external accessibility

Provide access

Specialist personnel

Installation of the smoke control damper

Installation according to the operating manual 

Ä

 5  ‘Installation’

on page 12

Install the smoke control damper correctly

Specialist personnel

Connection of smoke extract ducts/cover grille/flexible connector

Ä

 6  ‘Smoke extract duct and cover grille’ on page 27

Connection according to this manual

Establish correct connection

Specialist personnel

Supply voltage for the actuator

Power supply according to the actuator rating plate

Provide correct voltage

Skilled qualified electrician

A / B

Check of the smoke control damper for damage

Smoke control damper, damper blade and seal must be intact

Repair or replace the smoke control damper

Specialist personnel

Functional test of the smoke control damper 

Ä

 8.2  ‘Functional test’

on page 30

Actuator function OK

Damper blade closes

Damper blade opens

Determine and eliminate the cause of the fault

Replace actuator

Repair or replace the smoke control damper

Specialist personnel

C

Cleaning the smoke control damper

No contamination in the interior or on the exterior of the smoke con-

trol damper

Remove contamination

Specialist personnel

Interval

A = Commissioning

B = Regularly

The functional reliability of smoke control dampers must be tested at least every six months. If two consecu-

tive tests are successful, the next test can be conducted one year later.

C = As required, depending on the degree of contamination

Maintenance work

Item to be checked

Required condition

Remedial action if necessary

Maintenance

 

 

Smoke control damper Type EK-EU

32

Summary of Contents for EK-EU

Page 1: ...Smoke control damper Type EK EU Installation and operating manual Read the instructions prior to performing any task according to EN12101 8 Declaration of Performance DoP EK EU 002 GB en...

Page 2: ...e original Valid from 01 2017 TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Germany Germany Phone 49 0 2845 2020 Fax 49 0 2845 202 265 E mail trox trox de Internet http www troxtechnik com 04 2...

Page 3: ...shing content Copying content Translating content Microcopying content Saving content to electronic systems and editing it TROX Technical Service To ensure that your request is processed as quickly as...

Page 4: ...not avoided may result in property damage ENVIRONMENT Environmental pollution hazard Tips and recommendations Useful tips and recommendations as well as informa tion for efficient and fault free oper...

Page 5: ...solid ceiling slabs 17 5 5 1 Mortar based installation 17 5 6 Fire resistant smoke extract ducts 19 5 6 1 In horizontal or vertical smoke extract ducts 19 5 6 2 Leading from vertical smoke extract du...

Page 6: ...se in accordance with a fire protection concept that is based on the protection goal can authorise further installation options in air conditioning and ventilation systems also Incorrect use WARNING D...

Page 7: ...ampers EN 13501 4 Fire classification of construction products and building elements Fire resistance tests on compo nents of smoke control EN 1751 Ventilation for buildings Air terminal devices Declar...

Page 8: ...00 750 800 L mm 600 800 200 39 42 45 48 50 53 56 59 62 79 83 86 90 250 42 45 48 51 54 57 60 63 66 84 87 91 95 300 45 48 51 54 57 60 63 66 69 88 92 96 100 350 48 51 54 57 60 63 67 70 73 93 97 101 105 4...

Page 9: ...89 1300 101 107 112 117 123 128 133 139 144 180 186 192 198 1400 107 113 118 124 129 135 140 146 151 189 196 202 208 1500 113 118 124 130 136 141 147 153 159 199 205 212 218 2 3 Open Close actuators O...

Page 10: ...ible take the product in its transport packaging up to the installation location Transport protection devices The EK EU is delivered with cardboard transport protec tion that stabilises the casing dur...

Page 11: ...dampers remain closed For smoke extract the smoke control dampers in the affected fire compartment open so that smoke can be extracted All other smoke control dampers remain closed In the event of a f...

Page 12: ...of the smoke control damper Install the smoke control damper without torsion horizontal vertical Mortar based installation The perimeter gap s must be large enough so that mortar can be filled in even...

Page 13: ...n both sides of the damper installation and operating side Insert screws both from the top damper and from the bottom damper do not insert all screws in one line but pre drill in an offset pattern Fig...

Page 14: ...t the bottom Be sure to attach the boards to each other and also to attach them to the brick structure To do so use glue or screws Fig 9 3 screws should be at 200 mm from each other Boards Thickness m...

Page 15: ...nt sleeve joints between the damper and the duct in the wall the damper can alternatively be placed outside the wall in the flow of the approved smoke extract duct 5 6 Fire resistant smoke extract duc...

Page 16: ...t be closed off with mortar Entrapped air is to be avoided Connect the smoke extract duct to the EK EU 27 Follow the manufacturer s instructions here also Installation Supporting construction solid wa...

Page 17: ...f actuator casing under ceiling slab Fig 11 2 with casing length L 800 mm For ceiling thickness 150 mm casing length L 800 mm The connection of a fire resistant smoke extract duct above the ceiling is...

Page 18: ...dry wall screws pre drill holes with 3 mm 150 mm distance between screws Connect the smoke extract duct to the EK EU 27 Follow the manufacturer s instructions here also Installation while constructing...

Page 19: ...sted to EN 1366 8 gross density 500 kg m wall thickness 35 mm or equivalent e g Promat type AD40 or L500 d 40 mm 1 Insert smoke control damper into the fire resistant smoke extract duct and suspend it...

Page 20: ...smoke extract ducts with a solid design shaft Here installation is in the wall as per 5 4 Supporting construction solid walls on page 15 Personnel Specialist personnel Materials For angle section str...

Page 21: ...angle sections at the joints at the smoke extract duct and the smoke control damper then link the sections with steel staples distance 150 mm Connect the smoke extract duct to the EK EU 27 Follow the...

Page 22: ...g Promat type AD40 or L500 d 40 mm Glue e g Promat K84 or equivalent Steel staples 63 11 2 1 53 mm Requirements Smoke extract duct fire resistant tested to EN 1366 8 gross density 500 kg m wall thick...

Page 23: ...the angle sections at the joints at the smoke extract duct and the smoke control damper then link the sections with steel staples distance 150 mm Connect the smoke extract duct to the EK EU 27 Follow...

Page 24: ...board d 35 mm or equivalent Angle section by others Dry wall screws 4 100 mm Steel staples by others Personnel Specialist personnel Materials For angle section strips of fire rated PROMATECT LS board...

Page 25: ...a fire resistant smoke extract duct underneath the smoke control damper according to the manufacturer s instructions 4 Connect the fire resistant smoke extract duct to the smoke control damper by plac...

Page 26: ...rod 22 35 52 70 96 150 5 7 2 Fixing to the ceiling slab Fig 16 Fixing to the ceiling slab 1 Fire rated anchor with suitability certificate 2 Push through installation Use only fire rated steel anchors...

Page 27: ...lity of the smoke control damper is not affected connection according to assembly and operating manual of the smoke control damper The sizing of the smoke extract duct used remains the responsibility...

Page 28: ...Cover grilles If no smoke extract duct is connected to the smoke con trol damper a cover grille galvanised steel mesh aper ture 20 mm may be fixed instead to protect that side of the damper 6 3 Inspe...

Page 29: ...everal actuators can be connected in parallel as long as the performance specifications are taken into consideration Actuators with 24 V AC DC Safety transformers must be used The connecting cables ar...

Page 30: ...tion Position indicator OPEN position Socket for the crank handle Requirement The smoke control damper is closed 1 Insert the crank handle into the socket Fig 22 4 the crank handle is clip fixed to th...

Page 31: ...ng on where dampers are installed country specific regulations may apply Maintenance The smoke control damper and the actuator are mainte nance free with regard to wear but smoke control dampers must...

Page 32: ...damage Smoke control damper damper blade and seal must be intact Repair or replace the smoke control damper Specialist personnel Functional test of the smoke control damper 8 2 Functional test on page...

Page 33: ...ply before working on any electrical equipment 1 Disconnect the wiring 2 Remove the smoke extract ducts 3 Close the smoke control damper 4 Remove the smoke control damper Disposal ENVIRONMENT Risk of...

Page 34: ...stant smoke extract duct 19 20 22 24 Functional test 30 H Hotline 3 I Inspection 31 32 Inspection access 28 Installation position 12 Installation situations 12 L Limitation of liability 3 M Maintenanc...

Page 35: ...Smoke control damper Type EK EU 35...

Page 36: ...Valid from 01 2017 TROX GmbH Heinrich Trox Platz 47504 Neukirchen Vluyn Ger many Germany Phone 49 0 2845 2020 49 0 2845 202 265 E mail trox trox de http www troxtechnik com...

Reviews: