Classification:
E
600
120 (h
od
- i <-> o) S1500 C
mod
AA single
Personnel:
Specialist personnel
Requirements:
Sheet steel duct for increased operating tempera-
tures
The actuator must remain accessible for mainte-
nance work after installation
1.
Manufacture sheet steel duct
➂
and cut to length
according to manufacturer's instructions.
2.
Apply HT sealing tape
➅
to the flange of the
smoke control damper
➀
for sealing.
3.
Manufacture suspension
➁
for smoke control
damper
5.6 ‘Suspending the smoke control
4.
Screw smoke control damper to the sheet steel
duct with hexagon bolts, washers and nuts
➃
.
5.
In addition, connect the smoke control damper
with duct clips
➄
or alternatively self-tapping
screws
Chapter 6.1 ‘Smoke extract ducts’
.
Installation
Sheet steel smoke extract duct > In a vertical duct
Smoke control damper EK-JS
31