7.3.2 B230
Fig. 22: Wiring example 230 V AC
①
Switch for opening and closing, to be provided by others
②
Indicator light for CLOSED position, to be provided by others
③
Indicator light for OPEN position, to be provided by others
Technical data for open/close actuators
Order code detail
B230
Actuator
BEN230 TR
BEE230 TR
BE230 TR
Supply voltage
AC 198 … 264 V 50/60 Hz
Power consumption – when running
4 W
3.5 W
8 W
Power consumption – when idle
0.4 W
0.5 W
Power consumption rating
7 VA
6 VA
15 VA
4 A, Imax. (5 ms)
7.9 A, Imax. (5 ms)
Torque
15 Nm
25 Nm
40 Nm
Run time
< 30 s (90°)
< 60 s (90°)
< 60 s (90°)
Limit switch
Type of contact
2 changeover contacts
Switch rating
1 mA...3 A (0.5 A inductive),
1 mA...6 A
(0.5 A inductive),
Switching voltage
5 V DC...250 V AC
Open
5°
3°
Close
80°
87°
IEC protection class
II
Protection level
IP 54
Operating temperature
-30...55 °C
-30...50 °C
Connecting cable
Actuator
1 m, 3 x 0.75 mm², halogen-free
Limit switch
1 m, 6 x 0.75 mm², halogen-free
CE conformity according to
2014/30/EU, 2014/35/EU
Electrical connection
Actuators > B230
Smoke control damper EK-JS
41
Summary of Contents for EK-JS
Page 53: ...Decommissioning removal and disposal Smoke control damper EK JS 53...
Page 54: ...11 Flange dimensional drawing Flange dimensional drawing Smoke control damper EK JS 54...
Page 57: ...Smoke control damper EK JS 57...
Page 58: ...Smoke control damper EK JS 58...