Accessories 1
Installation kit – for installation adjacent to solid walls
06/2015 – DE/en
FK-EU
1
/
WV
/
Order code detail
Application
– Dry mortarless installation adjacent
to solid walls requires an installation kit
– The installation kit is used for the refurbishment
of old fire dampers that have been mortared in,
or for the connection to a sheet steel duct
that has been mortared in; with x
≤
260 mm
– Fire damper and installation kit
are supplied partly assembled
– Assembly and installation are
to be performed by others
– Fire dampers with installation kit
only with casing length L = 500 mm
– The fire damper and the installation kit
must be installed and secured according
to the fire damper operating and installation
manual and the WV installation manual
Materials and surfaces
– Installation kit made from special insulation
material and mineral wool strips
– Fixing elements made of galvanised steel
Description
K 4 – 1.1 – 20
Installation kit for dry mortarless installation adjacent to solid walls, with x
≤
260 mm
L [mm]
Order code
500
WV
FK-EU with installation kit WV
L = 500
Î̞ʹʽʷ
ݣ
ݣ
ݢ
ݢ
ݣ
ݢ
ݢ
ݢ
ݣ
ݤ
Installation kit WV, consisting of:
①
Installation kit
②
Fixing elements
③
Fire damper or duct section up for refurbishment
(by
others)