Distances
Fig. 13: Overview of distances
*
mixed installation with fire damper Type FKRS-EU
Distances (unless otherwise specified in the respective installation details)
Installation type
x [mm]
y [mm]
z [mm]
Mortar-based installation
40 – 225
60 – 225
≤
225
Fire batt installation
40 – 600
≥
200
2
40 – 600
Partial mortaring
1
~ 50
60 – 225
≤
225
1
solid wall only
2
Installation into separate installation openings
Installation orientations (see installation details for fire resistance properties)
Supporting construction
Installation type
Mortar-based instal-
lation
Dry mortarless
installation
Fire batt installation
Solid wall
A – F
A, B, D – F
Gypsum wall boards
E, F
Lightweight partition wall with metal support
A – F
E, F
A, B, D – F
Timber stud wall / half-timbered construction
A, B, D – F
E, F
A, B, D – F
Solid wood wall / cross-laminated timber wall
E, F
E, F
E, F
Shaft wall
A – F
E, F
Solid ceiling slab
A, B, D – F
E, F
In / in combination with solid wood ceiling
E, F / A, B, D – F
In / in combination with wooden beam ceiling
E, F / A, B, D – F
Installation
General installation information
Fire damper Type FKA2-EU
30