Installation with installation kit WE remote from
walls and ceilings
Casing length L = 500 mm
The installation kit must be mounted on the fire
damper by others.
Installation is carried out on sheet steel ducts
without any openings, with fire-resistant cladding.
The wall / ceiling slab connections as well as lead-
throughs must be made according to these instruc-
tions. Fittings must be configured according to
Promat® specifications.
Cladding and the wall / ceiling slab connection must
be made on 4 sides. Enough clear space is required
to attach to the wall, at least 155 mm around the
perimeter.
Fire dampers remote from walls and ceiling slabs
must be suspended or fixed.
Suspension systems with L
≥
1.5 m require fire-
resistant insulation. This is done with panel mate-
rials or mineral wool insulation according to the
respective manufacturer's specifications.
For further installation details and components to be
provided by others, see the respective installation
situation and the Promat manual.
Installation with fire batt
The distance from the operating side flange to the
wall or ceiling has to be 195 mm.
Fire batt systems consist of two layers of mineral
wool slabs, gross density
≥
140 kg/m³.
Apply fire-resistant sealant to the cut faces of the
mineral wool slabs and fit them tightly into the instal-
lation opening. Seal any gaps between the mineral
wool slabs and the installation opening, gaps
between the cut faces of cut-to-size pieces, and
gaps between slabs and the fire damper by applying
fire-resistant sealant or coating. Use only sealant or
coating that is suitable for the fire batt system.
Apply ablative coating to the mineral wool slabs,
joints, transitions and any imperfections on the
coated mineral wool slabs; coating thickness
≥
2.5 mm.
No use in combination with a flexible ceiling joint.
Fix fire dampers on both sides of the wall.
If the ceiling is fairly thick, you may use additional
layers of mineral wool slabs on side A.
Fig. 19: Fire-resistant sealant
1
FKA2-EU
2.4
Coated board system
8.21 Firestop sealant
Installation
General installation information
Fire damper Type FKA2-EU
34