Additional requirements: lightweight and compartment walls with metal support structure
Lightweight partition wall or compartment wall, see
Installation type
Installation opening [mm]
B1
H1
B2
H2
Mortar-based installation
1
B + 450 max.
H + 450 max.
B1 + (trim panels)
H1 + (trim panels)
Dry mortarless installa-
tion with
installation kit ES
1, 2
B + 140
H + 140
Dry mortarless installa-
tion with fire batt
3
B + 80 to 1200
H + 80 to 1200
B1 + (2
×
/ 4
×
trim
panels)
H1 + (2
×
/ 4
×
trim
panels)
1)
Trim panels optionally or corresponding installation details (max. 2
×
12.5 mm / 1
×
25 mm)
2)
Installation opening tolerance
±
2 mm
3)
Trim panels according to installation details required
Subsequent installation
Fig. 28: Subsequent installation in lightweight partition wall for clear opening
≤
475 mm between two shelves,
mortar-based installation shown (also applicable for dry mortarless installation)
1
FKA2-EU
2.1
Mortar
3.2
Lightweight partition wall with metal support struc-
ture, cladding on both sides
5.1
Dry wall screw, with a distance of
≤
100 mm
7.1
UW sections, cut to size by others, overlapping
Installation
Lightweight partition walls and compartment walls with metal support structure
Fire damper Type FKA2-EU
43