Fig. 30: Dry mortarless installation into a lightweight partition wall, with installation kit ES
1
FKA2-EU
2.9
Installation kit ES
3.2
Lightweight partition wall with metal support
structure, cladding on both sides
5.15
Bracket
6.2
Mineral wool,
≥
1000 °C,
≥
80 kg/m³ (required for
wall thicknesses > 100 mm)
6.5
Mineral wool (depending on wall construction)
6.11
Insulating strip (depending on wall construction)
7.10
Trim panels
7.13
Cladding
7.14
Reinforcing board of the same material as the
wall
H1/B1
Installation opening, see table
Z
For fixing, see Fig. 16 to Fig. 18
Up to EI 60
–
EI 30 S
Additional requirements: dry mortarless installation with installation kit ES in lightweight partition walls
Lightweight partition wall
Casing length L = 500 mm
Distance from the fire damper to the adjacent structural elements
≥
110 / 120 mm (depending on the arrange-
ment of brackets, 4-sided metal section)
65 – 70 mm distance between the fire damper with a shortened installation kit and load-bearing structural ele-
ments, see / , detail
≥
200 mm distance between two fire dampers in separate installation openings
Installation
Lightweight partition walls and compartment walls with metal support structure > Dry mortarless installation
with installation kit ES
Fire damper Type FKA2-EU
45